GRANUDOS 45/100 PLUS V70 Touch
Index: 03
Change date: 25.04.2018
Operating instructions no.: BA SW 001-03 Granudos 45-100 PL V70T.docx
Page 76 of 92
Switch contact to the appropriate fault message:
Description
Situation
Switch contact Display on
touch screen
Dosing device
1.
D-min. alarm
,
MWP rinsing tray
No pressure on pumps
open
1
2.
W-min. alarm
,
rinsing tray
floater down,
closed
1
3.
W-max. alarm,
rinsing tray
floater up,
closed
1
4.
Df-min. alarm
,
rinsing tray
switching body down,
closed
1
5.
Chlorine missing
alarm
No granulate in the cyclone
open
1
6.
Chlorine reserve
message
The amount set has been dosed
---
green
7.
Chlorine empty,
alarm
No chlorine
open
red
8.
Acid reserve
message
The amount set has been dosed
---
green
9.
Acid empty, alarm
acid container
floater down,
open
red
10.
"Chlorine motor"
alarm
Chlorine motor fuse triggered
---
red
Feed system
11.
Level min. message
buffer tank
floater down,
closed
green
12.
Level max. message
buffer tank
floater up,
closed
green
13.
Level min. alarm
,
buffer
tank
floater down,
closed
red
14.
Level max. alarm,
buffer tank
floater up,
open
red
15.
Collecting tray level
alarm
floater up,
closed
red
16.
pH-monitoring
alarm
pH-value not within tolerance range
closed
red
17.
Feed pump motor
protection alarm
Motor protection switch is triggered
closed
red
Other
18.
CCS (Central Control
System) off, message
Input central control system,
open
Central control
system externally
switched off
19.
Feed pump externally
switched off, message
Input externally switched off
open
Feed pump
externally
switched off