26
15. Technical data
15.1 Device data
The technical data of the module is given in the table below.
No.
Parameter
Data
Explanations
1
Location
Switch cabinet
DIN-rail mounting
2
Enclosure
IP20
Protection against foreign bodies
and water to IEC 529 (DIN 40050)
4
Service life
10 years
5
Housing size
23 × 111 × 115 mm
(screw-plug-connector included)
23 × 100 × 115 mm
(screw-plug connector not included)
W × H × D
6
Installation position
Any
7
Weight
Approx. 140 g
8
Operating temperature
0 °C…+55 °C
9
Storage/transport temperature
–40 °C…+70 °C
10
Atmospheric pressure
during operation
during transport
795 hPa…1080 hPa
660 hPa…1080 hPa
11
Installation altitude
2000 m
4000 m
Unrestricted
Restricted –
Ambient temperature
≤
40 °C
12
Relative humidity
Max. 80 %
No condensation,
no corrosive atmosphere
14
External
power supply
10…33 V DC
Standard power supply unit to
DIN 19240
15
Current consumption at 24 V DC Typ. 120 mA
max. 150 mA
17
Reverse voltage protection
Ja
But does not function!
18
Short-circuit protection
Ja
19
Overload protection
Poly-Switch
Thermal fuse
20
Undervoltage detection (USP)
≤
9 V DC
21
Emergency power supply
≥
5 ms
Device fully operable
Table: Technical data of the module