background image

14

10.2.1  Data structure

10.2.2  Fieldbus parameters

Trigger byte: See "The trigger byte", Chapter  9.13‚ on page 24
Length byte: See "The length byte", Chapter  9.14‚ on page 25

10.2.3  RS-232 parameter table

10.2.3.1 Start character (232 Start character)

If this character is defined, the gateway evaluates only the data at the RS-232 interface following this start character. Each trans-
mission from the gateway via the RS-232 interface is initiated with the start character in this case.

10.2.3.2 Length 232 (232 Length)

If this byte is activated, the gateway, at the receive end, awaits as many bytes of useful data as specified in this byte by the RS-232 
transmitter. At the transmission end, the gateway then sets this byte to the number of useful data items transmitted by it. If byte 
"Length232" is not defined, the gateway, on reception at the RS-232 interface, waits for the end criterion if this is defined. If no 
end criterion is defined either, as many characters as can be transferred in the fieldbus transmit buffer are read in via the RS-232 
interface.
As a special case for this parameter also a length byte with additional Timeout monitoring can be set in WINGATE. In that case the 
received characters will be discarded at a Timeout.

Attention:
If "Timeout“ is selected as end character, then this byte has no significance.

10.2.3.3 Data Area

In this data area the user data will be transferred.

10.2.3.4 End character (232 End character)

If this character is defined, the gateway receives data from the RS-232 interface up to this character. The "Timeout" criterion can 
be defined as a special case. In this case, the gateway continues to receive characters until a defined pause occurs. In the special 
case "Timeout" the "Length 232-byte" has no significance. At the transmit end, the gateway inserts the end character, if defined, 
as the last character of a transmission.

10.2.4  Communication sequence

The useful data (data area) arriving via the fieldbus is copied in accordance with chapter 10.2.1 transparently into the RS-232 
data field and transferred via the RS interface, whereby the protocol is supplemented in accordance with the configuration (start 
character, end character…). NO acknowledgement is issued !

If the "Trigger byte“ (see chapter 10.5) is active, data is sent only on a change of this byte. If the "Length byte" (see chapter 10.6) 
is active, only as many of the following bytes as specified there are transferred.

Trigger

(optional)

LengthBus
(optional)

Start signal

(optional)

Length232
(optional)

End signal
(optional)

Data field

Fieldbus

Data structure Universal 232 protocoll

Data field

RS

Содержание ZAG45FN01

Страница 1: ...Operating Instructions Fieldbus Gateway Fast Ethernet V 1 3 ZAG45FN01 ZUB CD FB...

Страница 2: ...the Debug mode 10 7 3 Communication parameter for the Debug interface 10 7 4 Possibilities with the Debug interface 10 7 5 Commands of the Debug interface 10 8 Mode of operation of the system 10 8 1...

Страница 3: ...1 Hardware ports switches and LEDs 18 11 1 Device labeling 18 11 2 Connectors 18 11 2 1 Connector to the external device RS interface 18 11 2 2 Connector supply voltage and DEBUG interface 19 11 2 3 E...

Страница 4: ...ights of granting of patents or registration of utility model patents 13 2 4 General information on line routing 23 13 2 4 1 Shielding of lines 23 14 Representation of the data in Ethernet TCP IP 24 1...

Страница 5: ...ing the module 2 also follow the rules below on installation of the equipment and on working on switch cabinets 1 4 Installation of the unit Modules must be installed in electrical equipment rooms are...

Страница 6: ...ctrically isolated 10 100 Base T interface to Ethernet Ethernet controller W3100A and REALTEK RTL8201CP Microprocessor 89C51 RD2 RAM and FLASH Optionally electrically isolated on the RS side Serial in...

Страница 7: ...nging the switches S4 and S5 in position E All other switches will not be taken into consideration for the setting of the test mode Now the Gateway has to be restarted with these settings by a short d...

Страница 8: ...Baud Rate 5 3 Buffer sizes at the Fieldbus Gateway Fieldbus Gateway CL features at the serial side a buffer with the size of 1024 bytes for input data and output data each The FIFO of the application...

Страница 9: ...into the device Open WINGATE and activate the device in the configuation mode see chapter 4 1 Configurati on mode config mode an actuation message appears that looks in line with the following exampl...

Страница 10: ...ossesses all cha racteristics a software development tool is typically supposed to have However it is also possible to carry out a Scrip update via this interface From Script version 27 on you can als...

Страница 11: ...ed reasonably There are no fixed rules how which Scripts have to operate properly When writing a Script you should take into account on which target hardware the Script is to be executed so the necess...

Страница 12: ...f baud rates at a 40 MHz crystal frequency with the corresponding errors 4800 baud 0 16 9600 baud 0 16 19200 baud 0 16 38400 baud 1 35 57600 baud 1 35 62500 baud 0 115200 baud 1 35 312500 baud 0 62500...

Страница 13: ...hould be too large in spite of these measures there is the possibility to generate a customized Script com mand that executes several tasks in one Script command Please contact our support department...

Страница 14: ...characters will be discarded at a Timeout Attention If Timeout is selected as end character then this byte has no significance 10 2 3 3 Data Area In this data area the user data will be transferred 1...

Страница 15: ...low priority communication partners 10 3 3 Data communication 10 3 3 1 Initiation of data communication by the low priority user If the low priority user also receives an STX in response to a transmi...

Страница 16: ...request on demand necessitates the first byte in the fieldbus containing a trigger byte see chapter 10 5 This byte is not transferred to the Modbus and serves only to start a Modbus transmission For t...

Страница 17: ...gateway waits for a new inquiry from the Modbus Master 10 4 4 Fieldbus Gateway as Modbus ASCII Master On request For the description see chapter 10 4 2 Fieldbus Gateway as MODBUS Master 10 5 The trig...

Страница 18: ...lable at the plug accessible on the upper side of the device Pin assignment X1 3 pole and 4 pole screw type plug connector Pin No Name Function 1 Rx 232 Receive signal 2 Tx 232 Transmit signal 3 AP GN...

Страница 19: ...3 V DC The voltage supply is made through the 4 pole screw plug connector at the device s bottom side Please note that the devices of the series Fieldbus Gateway should not be operated with AC voltage...

Страница 20: ...2 switchable Rx 422 terminating resistor for the serial interface Termination Tx 422 switchable Tx 422 or RS 485 terminating resistor for the serial interface Rotary coding switch S4 ID High for seria...

Страница 21: ...en two error categories Serious errors 1 5 In this case the Gateway must be switched off and switched back on again If the error occurs again the Gateway must be exchanged and returned for repair Warn...

Страница 22: ...andard screw type terminals one lead can be clamped per connection point It is best to then use a screwdriver with a blade width of 3 5 mm to firmly tighten the screw Permitted cross sections of the l...

Страница 23: ...these interference currents themselves becoming an interference source Wherever possible use only lines with braided shield The coverage density of the shield should exceed 80 Avoid lines with foil sh...

Страница 24: ...se of the data communication TCP features all mechanisms that are required in order to open a connection and to guarantee a flawless data transfer across the network and then again close the connectio...

Страница 25: ...placed or rather websites image files and Java applets can be called up This way it is also possible to represent the dynamically changing data of an application that is connected to the serial inter...

Страница 26: ...Storage transport temperature 40 C 70 C 10 Atmospheric pressure during operation during transport 795 hPa 1080 hPa 660 hPa 1080 hPa 11 Installation altitude 2000 m 4000 m Unrestricted Restricted Ambie...

Страница 27: ...ster CSMA CD Master slave Master slave 4 Number of users Transmitters Receivers 512 512 1 1 32 32 5 Cable length Maximum Depending on baud rate 100 m 15 m no 1200 m 93 75 kBd 1200 m 312 kBd 500 m 625...

Страница 28: ...or downloaded free of charge from our homepage at www wenglor com 16 3 Installation The Fieldbus Gateway FE module features protection type IP20 and is thus suitable for switch cabinet use The device...

Страница 29: ...pm Friday from 8 am to midday wenglor sensoric gmbh wenglor Stra e 3 DE 88069 Tettnang Central office and sales department 49 0 7542 5399 0 Technical hotline 49 0 7542 5399 246 Email Technical hotlin...

Страница 30: ...18 Annex 18 1 Hexadecimal table Hex Decimal Binary 0 0 0000 1 1 0001 2 2 0010 3 3 0011 4 4 0100 5 5 0101 6 6 0110 7 7 0111 8 8 1000 9 9 1001 A 10 1010 B 11 1011 C 12 1100 D 13 1101 E 14 1110 F 15 111...

Страница 31: ...31 Sensoren f r Ihren Erfolg www wenglor com Sensoren f r Ihren Erfolg www wenglor com...

Отзывы: