8.11. Vendor-specific object (0x64)
The vendor-specific object 100 is used for configuration of the I/O ports and PoE ports etc.
Vendorspecific Object (0x64)
Class Attributes
ID
Name
Access
Keine Class Instanz vorhanden. Attribute 1 nicht benötigt da Revision == 1
Class Services
Code
Name
Keine Class Instanz vorhanden
Instance Attributes
ID
Name
Access
Supported by
1
Direction Register (16 bit) (see below)
Get/Set
all Switches
2
Power Monitoring (BOOL) (see below)
Get/Set
not ZAC51EN01
3
PoE Enable (8 bit) (see below)
Get/Set
not ZAC51EN01
4
WebServer Access (BOOL), 0= disable, 1=enable
Get/Set
all Switches
Instance Services
Code
Name
0x0E
Get_Attribute_Single
0x10
Set_Attribute_Single
The following table shows the assignment between the IO points of the direction register and the instances and
the pin assignment of the ports.
Ports/Pins
IO LED
Assembly Bit
DIP/DOP Instance
0 / 2
0.0
0
1
0 / 4
1.0
8
3
1 / 2
0.1
1
2
1 / 4
1.1
9
4
8.11.1 Configuration assembly for ZAC50EN01 and ZAC50EN02
The configuration of the inputs/outputs is made via a configuration assembly 100.
Configuration Assembly (0x64)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Direction Access (Byte 0), (0=input (def.), 1=output)
1
Direction Access (Byte 1), (0=input (def.), 1=output)
2
Reserved
PM 0=off
1=on
3
PoE Enable/Disable (0=disable, 1=enable)
The abbreviation PM in the table refers to Power Monitoring.
8.11.2 Configuration assembly for ZAC51EN01
Configuration Assembly (0x64)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Direction Access (Byte 0) (see above)
1
Direction Access (Byte 1) (see above)