Wenglor SS2-00VA000R3 Скачать руководство пользователя страница 18

18

EN

4 Inputs

4.1 Test Input

A self-test is started at the control unit by applying 24 V DC to the test input (terminal 16). When the control  
unit’s safety inputs are activated, the control unit indicates that testing is being executed by shutting down the 
transmitters at the connected safety light barriers, and thus simulating penetration of the protected area. The  
operator must then check the effectiveness of the shut down. The transmitters are shut down for as long  
as 24 V DC is applied to the input.

The externally triggered test has no significance with regard to testing the control unit, because it is self-testing.

The test pulse has a minimum duration of 40 ms. Test frequency is based upon the risk analysis (safety  
regulations).

4.2 Acknowledgement Input

The control unit can be setup with either restart inhibit of automatic restart.

The use of restart inhibit (start and restart disabled) is required if the safety device is used to secure a passageway 
to the danger zone, and if it is possible for a person to be present in the danger zone without being detected after 
traversing the passageway.

4.2.1 Selecting the Mode of Operation
The following table depicts configuration of the operating modes.

Selecting the Mode of Operation

Terminal 6

Terminal 15

Mode of Operation

0 V not connected

24 V DC

Automatic restart

24 V DC

0 V not connected

Restart inhibit

0 V not connected

0 V not connected

Impermissible operation

24 V DC

24 V DC

4.2.2 Automatic Restart
In this operating mode, the control unit’s outputs correspond to the status of the light barriers:
• If the safety zone is unobstructed (light barrier outputs active), the relay outputs are activated.
• If the safety zone is obstructed (light barrier outputs inactive), the relay outputs are deactivated.

Содержание SS2-00VA000R3

Страница 1: ...SS2 00VA000R3 Individual Safety Light Barrier Control Unit Operating instructions Available as PDF only Status 02 05 2016 www wenglor com EN...

Страница 2: ...2 Parallel Approach to the Safety Field 10 2 4 Minimum Clearance to Reflective Surfaces 10 2 5 Mutual interference of the Light Barriers 11 3 Connection and Installation to the Machine 11 3 1 General...

Страница 3: ...ride 26 7 1 Basics 26 7 2 Settings 26 7 2 1 Selecting the Mode of Operation 26 7 2 2 Override with Continuous Command 27 7 2 3 Override with Command Pulse 27 8 Functions and Operation 28 8 1 Use of On...

Страница 4: ...14 Technical Data 32 14 1 Safety Light Barriers 32 14 2 Individual Light Barrier Control Unit 33 15 Checklist 35 16 Certification 35 17 EC Declaration of Conformity 36 17 1 Declaration of conformity...

Страница 5: ...us motion can be stopped electrically by the safety output of the Individual Light Barrier Control Unit The use of a type 2 safety device is permissible in accordance with the risk analysis After comp...

Страница 6: ...bots 1 3 2 Multiple Barrier Protection Use for access monitoring 1 3 3 Muting Function Safety Light Barrier Receiver Muting Sensor Receiver 1 Muting Sensor Receiver 2 Safety Light Barrier Transmitter...

Страница 7: ...types 1 5 Explanation of Utilized Symbols Makes reference to a measure for the prevention of a concrete danger Illustrates suggestions and instructions which make use of the controller easier 2 Import...

Страница 8: ...ion to the line of detection or to the safety field K Approach speed constant in mm per sec 1600 mm per sec T Total response time t1 t2 in seconds t1 Response time of the Individual Light Barrier Cont...

Страница 9: ...t1 t2 C 1200 mm Direction of Approach If more than one light barrier is used the table included below applies C Margin for penetration into the dan ger zone before the safety device is tripped never...

Страница 10: ...0 4 H K 1600 mm per second S K t1 t2 C 1200 mm 0 4 H Direction of Approach S Minimum safety clearance H Height of the safety field 2 4 Minimum Clearance to Reflective Surfaces If reflective surfaces...

Страница 11: ...eceiver Emitter Receiver 3 Connection and Installation to the Machine 3 1 General The Individual Light Barrier Control Unit must be integrated into the system such that at least IP 54 protection is as...

Страница 12: ...ical motors inverters frequency variators as well as any other sources of interference The connector cables between the control unit and the sensors connector cables to the test command generator and...

Страница 13: ...d Off Channel 2 unobstructed or unused OSSD DIAG Green Red Yellow Red Output relay open Red blinking The number of pulses indicates the type of failure only when CH2 Failure is on Green Output replay...

Страница 14: ...p 23 section 6 2 3 24 V DC 4 Muting duration 1 I p 24 section 6 3 5 Muting duration 2 I p 24 section 6 3 6 Restart inhibit I p 19 section 4 2 3 7 Override 1 I p 26 section 7 8 Override 2 I p 26 secti...

Страница 15: ...input 1 I p 23 section 6 2 13 0 V 2 Muting input 2 I p 23 section 6 2 14 PE ground 3 24 V DC 15 Acknowledgement input I p 18 section 4 2 4 Muting duration 1 I p 24 section 6 3 16 Test input I p 18 sec...

Страница 16: ...ther Information 1 Muting input 1 I p 23 section 6 2 13 0 V 2 Muting input 2 I p 23 section 6 2 14 PE ground 3 24 V DC 15 Acknowledgement input I p 18 section 4 2 4 Muting duration 1 I p 24 section 6...

Страница 17: ...tion Input Output Further Information 1 Muting input 1 I p 23 section 6 2 13 0 V 2 Muting input 2 I p 23 section 6 2 14 PE ground 3 24 V DC 15 Acknowledgement input I p 18 section 4 2 4 Muting duratio...

Страница 18: ...can be setup with either restart inhibit of automatic restart The use of restart inhibit start and restart disabled is required if the safety device is used to secure a passageway to the danger zone a...

Страница 19: ...s acknowledgement input terminal 15 from a pushbutton or by means of an appropriate command for example from a PLC After penetration into the protected area the relay outputs are deactivated and can o...

Страница 20: ...tactor monitoring is used to determine whether or not external contactors or auxiliary contact elements func tion properly External contactors may only be connected if they are equipped with positivel...

Страница 21: ...Terminal Designation Input Output Further Information 1 Muting input 1 I p 23 section 6 2 13 0 V 2 Muting input 2 I p 23 section 6 2 14 PE ground 3 24 V DC 15 Acknowledgement input I p 18 section 4 2...

Страница 22: ...muting signal output The muting sensors serve as a receiving system which decides whether the muting function will be activated or deactivated Monitoring of the dangerous passageway is only interrupte...

Страница 23: ...must above all be adhered to when the material is uneven is shifted when it enters the muting zone or if its height changes 6 2 Connecting the Muting Sensors and the Muting Indicator 6 2 1 Muting Sens...

Страница 24: ...muting sensors and the muting indicator Any wenglor light barrier with an antivalent PNP output the output must read out 24 V as long as the light beam is unobstructed can be used as a muting sensor...

Страница 25: ...ing Sensor 2 Receiverr Muting Sensor 2 Receiver Muting Sensor 1 Transmitter Receiver Object which Triggers Muting After muting has been activated as a re sult of obstruction of both muting sen sors wi...

Страница 26: ...e the safety light barrier and or at least one muting sensor is obstructed The override display blinks in this case see section 8 3 The override mode sets the OSSD outputs to ON and makes it possible...

Страница 27: ...nd 8 or all safety light barriers and muting sensors are unobstructed or 15 minutes have elapsed since initial activation The last two points are reset after a complete muting sequence has been comple...

Страница 28: ...ed green yellow On Red Red Start up test Off Off Red Channel obstructed outputs off Off Green Red On Off Red On Green Yellow Channel unobstructed outputs off unit is waiting for restart On Green Green...

Страница 29: ...ting duration the muting indicator and override Off Red 6 pulses red Configuration changed without restart Switch the unit off an back on again to eliminate the problem Switch the unit off and back on...

Страница 30: ...nel CH1 CH2 The check list for initial operation Chapter 13 helps executing the testing 10 2 Daily Inspection and Maintenance Regular inspections must be completed in accordance with local ordinances...

Страница 31: ...accordance with all respectively valid national waste disposal regulations The housings of the individual Safety Light Barriers and the Individual Light Barrier Control Unit are made of plastic and c...

Страница 32: ...t Barrier Control Unit Light Barriers and the re quired Connector Cables must be ordered Operating instructions are included in the scope of delivery The transmitter and the receiver used for a given...

Страница 33: ...specified with this value After this point in time PFHd SIL and PL values can no longer be guaranteed and replacement of the relays becomes mandatory A T10d value of greater than 20 years means that t...

Страница 34: ...put 40 ms Muting sensor inputs 2 pairs of sensors transmitter receiver 24 V DC PNP Muting enable input 24 V DC PNP Override time limit 60 min Operating modes restart inhibit or automatic restart LED d...

Страница 35: ...ion Yes No Have additional mechanical protective measures been installed which prevent reaching under over or around the safety field and are they protected against manipulation Yes No 4 Installation...

Страница 36: ...36 EN 17 EU Declaration of Conformity 17 1 Declaration of conformity for Individual Safety Light Barrier Control Units SS2...

Страница 37: ...37 17 2 Declaration of conformity for Safety Through Beam Sensor SL2 w...

Отзывы: