Installation and operating instruction
Hydraulic unit WWP LS 8 ... 16-B
6 Operation
83306902 2/2017-05 La
49-88
Parameters
Setting
Building
With weather compensated control the mixed external temperature influences the
flow setpoint temperature. The influence depends on the building construction.
The better (heavier) the building construction, the slower the influence.
Off, light, medium, heavy
Minimum temperature
Lower limit for the minimum flow temperature. Lower heat demands are limited to
the value set.
Maximum temperature
Upper limit for the maximum flow temperature. Higher heat demands are limited to
the value set.
Demand increase
The flow setpoint temperature of the heating circuit is increased by the value set,
e. g. to compensate for load losses.
Screed program
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
55
45
35
25
0
2
1
3
4
1
Days
2
Flow setpoint temperature [°C]
3
Function specific heating
4
Screed drying
6.7.3.5 Summer/Winter change-over
Heating circuit
Su/Wi
change-over
Setting
Description
3.0 … 30.0°C
If the average external temperature exceeds the value set, the operating mode
changes to
Summer
.
OFF
The operating mode set remains activated, independent of the external temperat-
ure.
6.7.3.6 Time programs
Heating circuit
Time
programs
The heating program is used to stipulate the times of the day when comfort, normal
or setback heating is used.
The time program can be adapted individually [ch. 6.4.3].
The heating program is only activated in operating mode
Heating
.