Installation and operating instruction
Oil condensing boiler WTC-OB 18-B
6 Operation
83311002 1/2018-03 La
41-132
6.3.2 Parameter level
Display parameter (
P
)
Activate parameter level [ch. 6.3].
Turn dial knob.
System values can be read.
Depending on system variation, specific parameters are shown or hidden.
Change values
Press [ENTER].
Value set will be shown flashing.
Change values using the dial knob.
Save the value with the [Enter].
Parameters Basic configuration
Setting range
Factory
setting
P 10
Unit configuration
P 11
Operating mode
–
: no flue gas damper
A
: flue gas dampers (
P 15
,
16
,
17
are hidden).
–
P 12
Unit address
1
: single unit
A
…
E
: cascade DDC system
(
1
,
A
sets
P 71
to
1
)
1
P 13
Function variable output
MFA1
0
: operating retransmission
1
: forward reporting of faults
2
: feeder pump upstream of hydraulic de-couple
3
: heating circuit pump without WCM-FS
4
: DHW load pump; three way valve
5
: DHW circulation pump without WCM-FS via DHW re-
lease or via button (
P 17
to
4
)
6
: DHW circulation pump with WCM-FS via circulation pro-
gram
7
: heating circuit pump with WCM-FS #1
1
P 14
Function variable output
MFA2
0
: operating retransmission
1
: forward reporting of faults
2
: feeder pump upstream of hydraulic de-couple
3
: heating circuit pump without WCM-FS
4
: DHW load pump; three way valve
5
: DHW circulation pump without WCM-FS via DHW re-
lease or via button (
P 17
to
4
)
6
: DHW circulation pump with WCM-FS via circulation pro-
gram
7
: heating circuit pump with WCM-FS #1
1