7.4 Calculating the burner rating
V
B
Operating volume in m
3
/h (gas throughput)
V
N
Normal volume in m
3
/h (gas throughput at 0 °C and 1013 mbar)
V
G
Gas throughput determined at gas meter
T
M
Time measured during gas throughput determination (V
G
)
f
Conversion factor
t
Gas
Gas temperature at meter in °C
P
Gas
Gas pressure at meter in mbar
P
Baro
Barometric air pressure in mbar (see table)
Q
F
Combustion heat rating in kW
H
i
Calorific value in kWh/m
3
(at 0 °C and 1013 mbar)
Determine operating volume (gas throughput)
▶
Measure gas throughout V
G
at gas meter, measuring time T
M
should be a minimum
of 60 seconds.
▶
Calculate operating volume (V
B
) using the following formula.
Calculate conversion factor
▶
Determine gas temperature (t
Gas
) and gas pressure (P
Gas
) at gas meter.
▶
Determine air pressure (P
Baro
) from the following table.
Height
above sea
level (m)
0
100
200
300
400
500
600
700
800
900
1000 1100 1200 1300
P
Baro
in mbar
1013 1001 990
978
966
955
943
932
921
910
899
888
877
866
▶
Calculate conversion factor (f) using the following formula.
Calculate normal volume
▶
Calculate normal volume (V
n
) using the following formula.
Calculate burner rating
▶
Calculate burner rating (Q
Br
) using the following formula.
Installation and operating instruction
Gas condensing boiler WTC-GB 90-A
7 Commissioning