Installation and operating instruction
Gas condensing unit WTC-GB 15-B Compact and WTC-GB 25-B Compact
6 Operation
83309302 1/2018-05 La
93-196
6.6.8 Output test
During the output test, the actuators connected (pump, mixer, etc.) can be
switched manually for test purposes.
When exiting the parameter, the output test is automatically reset to
Off
.
6.6.8.1 WTC
Output test
WTC
Parameters
Setting
9.1.1
Output test
Off:
Output test WTC deactivated.
On
:
Output test WTC activated.
9.1.2
MFA1
Activate output MFA1.
Off
On
9.1.3
VA1
Activate output VA1.
Off
On
9.1.4
VA2
Activate output VA2.
Off
On
9.1.5
External PWM signal
Activate PWM signal.
0 … 100 %
6.6.8.2 EM heating circuit
Output test
EM heating
circuit
Parameters
Setting
9.2.1
Output test
Off:
Output test EM heating circuit deactivated.
On
:
Output test EM heating circuit activated.
9.2.2
Relay test
Activate output M1 or MM1.
Off
Pump
(M1)
Mixer Open
(MM1)
Mixer Closed
(MM1)
9.2.3
PWM signal
Activate PWM signal.
0 … 100 %