Содержание WRS

Страница 1: ...End user Weishaupt Controller System WRS 83051902 1 2003 Operating instructions manual ...

Страница 2: ...2 ...

Страница 3: ...5 Call up and change heating program 17 6 6 Call up and change hot water program 18 6 7 Call up and change timer program only possible on the WRS CPU B2 E 19 6 8 Call up and change temperature setpoints 20 6 9 Call up and change heating reference line weather compensated 21 6 10 Energy saving function 22 6 11 Set holiday start end 23 6 12 Type of operation 24 6 12 1 Set type of operation call up e...

Страница 4: ...Parameter settings for your system 32 9 1 Parameter setting following commissioning 32 9 2 Equipment and configuration 34 9 3 Hand over to the customer 34 Notes 35 4 9 A ...

Страница 5: ...ept with the heating appliance The address and telephone number of the nearest service centre should be entered on the reverse of the operating instructions The plant operator must note that an agent of the contractor or other suitably qualified person must inspect the plant at least once a year To ensure regular inspections weishaupt recommends a service contract The contractor should instruct th...

Страница 6: ...ld be checked for signs of visible damage and to ensure that the safety devices are operating correctly More frequent safety checks may be required depending on plant conditions Electrical safety Work on the electrical supply should be carried out by a qualified electrician Electrical components should be checked during servicing Loose connections and damaged cables should be dealt with immediatel...

Страница 7: ...m holiday function etc Your heating engineer has access to further settings to ensure your heating system can be optimised to meet your requirements The Weishaupt controller system can be extended with Extension module WRS EM 8 additional modules for the control of heating circuits and their associated operating units 7 3 About the Weishaupt Controller System 3 The Weishaupt Controller System WRS ...

Страница 8: ...ting program Enter key Selections or changes are confirmed by pressing this key Dial knob By turning the current temperature setpoint can be displayed Error condition or service required Heating currently operating in economy mode Heating currently operating in normal mode Symbols on the display When operating the direct setting level please note The operating unit must be fitted to the boiler cov...

Страница 9: ...ing the button Heating to economy temperature when not present Heating to normal temperature when present Temporarily change from economy temperature to normal temperature Temporarily change from normal temperature to economy temperature info Note The setpoint adjustment affects only that unit who s address is shown on the display Reducing the room temperature by just 1 C can save up to 6 fuel The...

Страница 10: ...alues of the heating system are displayed one after the other The value remains as a continuous display relative to the selected information 1 Only shown on specific system versions 2 Not shown on address 0 A B C 3 Shown only on address 0 1 and 2 Note It can take up to 10 mins before the hot water sensor value is displayed 4 Shown only on address 1 5 Shown only on address 0 1 A B C Screed 15 41 Ho...

Страница 11: ...selection switch for type of operation On operating unit address 0 HE parameter 910 0 not possible Please note The display pictures shown only appear when the information about the type of operation is called up by pressing the Info button Otherwise the information last called up with the Info key remains displayed prog Standard heating program 1 Mon to Fri 06 00h to 22 00h Normal temp Sat and Sun...

Страница 12: ... all pumps The temperature limits which are given electronically by the controller are ignored The hot water temperature can become the same as the boiler temperature This depends on the position of the selection switch on the boiler control panel If the hot water temperature is 60 C it is possible to get scalded as any circulation pump fitted can also pump the hot water directly to the tap Note I...

Страница 13: ...4 Gradient 54 S W switchover 53 20 0 Function not active heating circuit switched off Function is activated once a value has been set shows that other parameter groups can be selected by turning the dial knob A flashing parameter value can be altered with the dial knob Operator shows that you are in the extended setting level 1 marks the selected heating circuit here heating circuit 1 Parameter nu...

Страница 14: ...52 Frost prot 53 S W switchover 54 Gradient 55 DHW setpoint 60 Holiday from 61 Holiday to 62 Holiday temp 70 Program 1 71 Error message 72 Burner runtime1 73 Burner start 1 74 Burner runtime21 75 Burner start 21 80 Parameter Reset 81 Service 82 Max val flue gas 21 Heat cycle Mon 27 Heat cycle Sun 28 Heat cycle week 1 Only displayed on WRS CPU B2 2 Only displayed on WRS CPU B2 E 3 Only shown for ad...

Страница 15: ...y shows To be able to alter the settings with the operating unit removed from its holder it needs the current boiler data This data must first be transferred from the boiler to the operating unit If you have altered the settings with the operating unit removed from its holder this data has to be transferred from the operating unit to the boiler Cancel unit selection info info Cancel unit selection...

Страница 16: ...tart 902 25 Mar Summer End 903 25 Oct Summer End 903 25 Oct Summer End 903 25 Oct Summer End 903 25 Oct Summer Start 902 25 Mar Summer Start 902 25 Mar or or or return return return continue Press Turn until display shows same procedure for minute year month day Note You must check all setting parameters one by one hour minute year month day as data is not automatically backed up when exiting the ...

Страница 17: ...r Heat program3 Heat cycle Mon 11 Heat cycle Mon 11 Heat cycle Tues 12 Heat cycle Wed 13 Heat cycle Heat cycle Week 18 Mo 1 Start06 00 11 Mo 2 Start 11 Mo 1 End 22 00 11 Mo 2 End 11 Mo 3 Start 11 Mo 3 Start 11 or next week day return If no entry at 2 Start Press Turn until display shows Press to call up heat program 1 select next heat programs press to call up heating cir cuit Monday If entry at 2...

Страница 18: ...dependant on the the heating program Example for 2 D H W cycles on one day 0h 6h 12h 18h 50 C 1 Start 1 End 2 Start 2 End 1 Cycle 2 Cycle Normal temperature Economy temperature 1 Operator DHW Program DHW Cycle Mon 41 DHW Cycle Mon 41 DHW Cycle Tues 42 DHW Cycle Wed 43 DHW Cycle Week 48 Mo 1 Start06 00 41 Mo 2 Start 41 Mo 1 End 22 00 41 Mo 2 End 41 Mo 3 Start 41 Mo 3 Start 41 or next week day retur...

Страница 19: ... level parameter 174 Prog 5 Example for 2 program cycles on one day 0h 6h 12h 18h Ein Aus 1 Start 1 End 2 Start 2 End 1 Cycle 2 Cycle On 1 Operator Program 5 ProgCycle Mon 1 ProgCycle Mon 1 ProgCycle Tues 2 ProgZ ProgCycle Wed 3 ProgCycle Week 8 Mo 1 Start06 00 1 Mo 2 Start 1 Mo 1 End 22 00 1 Mo 2 End 1 Mo 3 Start 1 Mo 3 Start 1 or next week day return If no entry at 2 Start Press Turn until displ...

Страница 20: ... out depending on the current external temperature but depending on an average external temperature determined over time External dampened With this the heating is switched off when the dampened external temperature is 2 C above the switchover temperature If the dampened external temperature is 1 C below the switchover temperature the heating circuit is re activated The dampened external temperatu...

Страница 21: ...ptation is enabled in the heating engineer level parameter 133 On the gradient is altered by this function the value set no longer corresponds to the one which was set 10 0 10 20 30 10 15 20 25 30 35 40 30 40 50 60 70 80 90 100 Tv C A C 5 T T R 30 20 10 0 C Raumsolltemperatur Raumsolltemperatur Heating reference line External temperature Flow temperature Determining the gradient of the heating ref...

Страница 22: ...ering the switchover temperature the relevant annual phases are either shortened or lengthened This conversion only affects the heating circuit Switchover temperature Increase Switchover to Winter operation earlier Switchover to Summer operation later Decrease Switchover to Winter operation later Switchover to Summer operation earlier Heating OFF Winter to Summer TEdamp DHL 1 C Heating On Summer t...

Страница 23: ...ing circuit must be selected Note Each heating circuit has to be set to holiday mode separately By switching contact H1 M the whole system can be reduced 1 Operator Holiday Holiday from 60 Holiday from 60 Holiday from 60 17 Sep Holiday from 60 17 Oct Holiday to 61 17 Oct Holiday to 61 Holiday temp 62 Economy temp Holiday from 60 Holiday to 61 17 Oct Holiday 61 17 Oct Holiday temp 62 Economy temp H...

Страница 24: ...ation Type operation 70 Program1 Type operation 70 Program1 Type operation 70 Summer Error message 71 Burner runtime1 72 Burner start 1 731 Burner runtime2 74 Burner start 2 75 or next parameter return Press Turn until display shows Note Burner run time and burner starts cannot be reset The type of operation can only be altered at addresses 0 and 2 if the heating circuit has not been assigned with...

Страница 25: ... No Service 81 Boiler Service 81 none Reset value Parameter reset 80 No Parameter reset 80 Yes return Press Turn until display shows Press for 3 seconds Max val flue gas 82 205 C Reset value Max val flue gas 82 145 C Press for 3 seconds Press to call up options Press to carry out settings Press to confirm settings Resetting the service message when service is due Resetting the message Flue gas lim...

Страница 26: ...e display shows all other values as shown at address 1 Note Often the data of the selected module has to be read if parameters are to be changed heating engineer level parameter 910 0 or 2 to ensure that current data is available After every alteration has been made which needs to be backed up the data has to be written heating engineer level parameter 930 Yes If this procedure is not followed som...

Страница 27: ...ustment only acts only on the heating circuit with address 2 on the other heating circuit the setpoint default must be changed via parameter 50 51 or 52 The room influence can be set depending on the heating circuit via parameter 130 On in the heating engineer level 7 4 Special features Address 2 address setting heating engineer level of WRS BE 1 Operator Type operation Unit selection 1 WRS CPU B1...

Страница 28: ...eating circuit via gravity principle Burner control circuit open T1 T2 Sensor short circuit or open circuit after sensor recognition Rectification Connect external sensor if necessary set parameter 141 Service level to On Connect external sensor to WRS EM apply voltage to CPU as external sensor is connected to the CPU Call up external temperature value in Info level If the value 0 0 C is displayed...

Страница 29: ...on the Bus enquiry By activating the sensor reset HE parameter 129 Yes the input can be speeded up Sensor not plugged in to its plug slot No 3 use correct plug slot The hot water circulation pump has seized loosen or replace pump Ball valve in connection set is closed open ball valve Pump not installed as per instructions change pump location Note The error message can be reset via Sensor Reset pa...

Страница 30: ...rameter 210 Flue gas sensor set to terminal B10 B7 Sensor short circuit or open circuit after sensor recognition by parameter 215 to Sensor B10 B11 Parameter 210 Flue gas sensor set to Terminal B9 B7 Rectification Connect calorifier sensor B10 Call up Top calorifiers in the Info level If is displayed the sensor has a short circuit If the display shows _ _ _ the sensor is open circuit The heating c...

Страница 31: ...be set to 8 3 Dwelling to cold or too warm 8 5 Pump run on time If the heating circuit or circuits are operating in an economy function Summer Winter Switchover day heating limit automatic the pump will be switched off 3 minutes after the condition temperature has been reached 8 6 Sensor recognition The connected sensors are stored once the control unit has had voltage applied for more than 2 hour...

Страница 32: ... Fri 06 00h to 22 00h Normal temperature 12 Heat cycle Tue 13 Heat cycle Wed 14 Heat cycle Thur 15 Heat cycle Fri 16 Heat cycle Sat Sat and Sun 07 00h to 23 00h Normal temperature 17 Heat cycle Sun 18 Heat cycle Week Heat program 2 21 Heat cycle Mon Mon to Fri 05 30h to 08 30h Normal temperature 22 Heat cycle Tue 12 00h to 22 00h Normal temperature 23 Heat cycle Wed etc Sat and Sun 07 00h to 23 00...

Страница 33: ...1 Heat cycle 2 Heat cycle 3 Day from to from to from to Mon Tue Wed Thur Fri Sat Sun Personal heating program 1 Heat cycle 1 Heat cycle 2 Heat cycle 3 Day from to from to from to Mon Tue Wed Thur Fri Sat Sun Personal heating program 2 Heat cycle 1 Heat cycle 2 Heat cycle 3 Day from to from to from to Mon Tue Wed Thur Fri Sat Sun Personal heating program 3 DHW cycle 1 DHW cycle 2 DHW cycle 3 Day fr...

Страница 34: ... heat circuit 1 CPU B3 for heat circuit 1 Extension module EM 2 for heat circuit 2 __________________ EM 3 for heat circuit 3 __________________ EM 4 for heat circuit 4 __________________ EM 5 for heat circuit 5 __________________ EM 6 for heat circuit 6 __________________ EM 7 for heat circuit 7 __________________ EM 8 for heat circuit 8 __________________ EM 9 for heat circuit 9 ________________...

Страница 35: ...35 Notes A ...

Страница 36: ... plant Thermo Unit The Thermo Unit heating systems from cast iron or Up to 55 kW steel Modern economic reliable For environmentally friendly heating Fuel Gas or oil as desired Thermo Condens The innovative condensing boilers with the SCOT system Up to Efficient low in emissions versatile Ideal for domestic 1 200 kW heating Floor standing gas condensing boiler with ratings of up to 1200 kW cascade ...