Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
7 Commissioning
83252902 1/2019-09 La
42-84
7.4 Concluding work
WARNING
Oil leakage from oil pressure measuring devices due to constant load
Oil pressure measuring devices could be damaged and cause environmental pollu-
tion through leakage.
Close or remove oil pressure measuring devices once commissioning is com-
plete.
Check control and safety devices.
Check tightness of oil carrying components.
Enter combustion values and settings in the commissioning record and/or test
sheet.
Inform the operator about the use of the equipment.
Hand the installation and operating manual to the operator and inform him that
this should be kept with the appliance.
Point out to operator that the installation should be serviced annually.