9 Servicing
83298002 3/2019-11 La
74-112
9.15 Replacing the combustion manager
Observe notes on servicing [ch. 9.1].
Unplug all plugs.
Undo screws
1
.
Push combustion manager upwards and replace.
1
Connect all plugs again.
Preset combustion manager
Unplug bridging plug No. 7 on combustion manager.
Switch on voltage supply.
The unprogrammed condition of the combustion manager is indicated by a flash-
ing display.
The burner goes to lockout.
Press [ENTER].
Burner has been reset.
Combustion manager drives to Standby.
If an oil pressure switch is fitted, set parameter
7
and
8
to
1
If an air pressure switch is fitted, set parameter
8
to
1
Press [G] and [L/A] simultaneously.
Combustion manager changes to access level.