7 Commissioning
83298002 3/2019-11 La
51-112
2. Adjusting the operating points
Open oil shut off devices.
If a controlled shutdown or lockout occurs during setting:
Briefly press [G] and [L/A] keys simultaneously.
Press [+] key.
Combustion manager changes to setting level.
Plug in bridging plug No. 7 on combustion manager.
Burner starts.
Speed standardisation starts.
Press [+] key within 20 seconds.
Speed standardisation is carried out.
U
and the current fan speed are displayed.
Wait approx. 5 seconds, until the fan speed has stabilised.
Press [+] key within 15 seconds.
Speed standardisation is complete.
Burner starts in accordance with program sequence and stops in operating
point P
0
(ignition position).