![Weishaupt WL40Z-A Скачать руководство пользователя страница 38](http://html1.mh-extra.com/html/weishaupt/wl40z-a/wl40z-a_manual_953361038.webp)
Installation and operating instruction
Oil burner WL40Z-A
7 Commissioning
83298002 3/2019-11 La
38-112
Measuring device for sensor current (continuous operation only)
Disconnect plug coupling on flame sensor LFS1.
Connect current measuring device
1
in series.
Flame signal flame sensor LFS1/RAR9
Extraneous light detection from
6.5 μA
Minimum flame signal
15 μA
1