Installation and operating instruction
Oil burner WL10/3-D
3 Product description
83292602 1/2019-04 La
16-76
3.4.6 Rating
Combustion heat rating
Combustion heat rating
50 … 90 kW
4.2 … 7.6 kg/h
(1
Combustion head
W10/3-D
(1
The oil throughput data relates to a calorific value of 11.9 kWh/kg for fuel oil EL.
Capacity graph
Capacity graph to EN 267.
The capacity data given relates to an installation elevation of 500 m above sea
level. For installation elevations above 500 m a capacity reduction of
approx. 1 % per 100 m applies.
A limited capacity graph is valid for ducted air intake.