Installation and operating instruction
Oil burner WL10/3-D Z
7 Commissioning
83292802 1/2019-04 La
30-80
7.1.2 Setting values
Set mixing head relative to the combustion heat rating required. For this, the dif-
fuser setting and the air damper setting should be matched.
Determine diffuser setting and air damper setting
Do not operate the burner outside of the capacity graph.
Determine the diffuser setting (dimension X) and air damper setting required
from the diagram and note down.
Example
Burner capacity stage 2 / stage 1 required
90 kW / 60 kW
Diffuser setting (dimension X)
8.8 mm
Air damper setting stage 2 / stage 1
59° / 32°
Diffuser default settings
3
4
5
6
7
8
9
10
11
55
60
65
70
75
80
85
95
100
105
90
1
2
1
Combustion heat rating [kW]
2
Diffuser settings (dimension X) [mm]
Air damper default settings
25
30
35
40
45
50
55
60
65
70
45
50
55
65
70
75
80
85
95
100
105
90
60
4
1
2
3
1
Combustion heat rating [kW]
3
Stage 1
2
Air damper setting [°]
4
Stage 2