Installation and operating instruction
Dual fuel burner WGL30/1-C ZM
4 Installation
83260202 1/2019-02 La
26-144
4.2 Selecting the nozzles
Determine the size of the nozzle relative to the load distribution.
Load distribution
The oil throughput at stage 2 equates to 100 % of the total load.
Divide total load (100 %) between the 2 oil nozzles:
stage 1 must lie within the capacity graph,
observe capacity range of boiler,
observe flue gas temperature (boiler, chimney),
observe heat demand,
observe start behaviour of burner.
Typical distribution of load, a different distribution may be required:
Nozzle 1: 55 %
Nozzle 2: 45 %
Example
Burner capacity required: approx. 280 kW
55 % of burner capacity required: 275 kW × 0.55 = 154 KW
45 % of burner capacity required: 275 kW × 0.45 = 126 kW
Nozzle size at 12 bar, see nozzle selection table:
Nozzle 1 (148.8 kW): 3.00 gph
Nozzle 2 (135.7 kW): 2.75 gph
Recommended nozzles
Make
Characteristics
Fluidics
45°HF
Pump pressure setting
10 …
12
… 14 bar
Spray characteristic and spray angle varies depending on pump pressure.
Содержание WGL30/1-C ZM
Страница 1: ...Installation and operating instruction Dual fuel burner WGL30 1 C ZM 83260202 1 2019 02 ...
Страница 121: ...Installation and operating instruction Dual fuel burner WGL30 1 C ZM 12 Project planning 83260202 1 2019 02 La 121 144 ...
Страница 138: ...Installation and operating instruction Dual fuel burner WGL30 1 C ZM 14 Notes 83260202 1 2019 02 La 138 144 14 Notes ...
Страница 139: ...Installation and operating instruction Dual fuel burner WGL30 1 C ZM 14 Notes 83260202 1 2019 02 La 139 144 ...
Страница 143: ...83260202 1 2019 02 La ...