Installation and operating instruction
Gas burner WG20…/1-C LN
10 Troubleshooting
83240802 1/2020-01 La
68-96
Error codes with lockout
The following faults must only be rectified by qualified personnel:
Fault codes
Fault
Cause
Rectification
2 x flashing
No flame,
end of safety time
No ignition
Ignition electrode set incor-
rectly
Set ignition electrode
[ch. 9.5]
Ignition electrode dirty or
wet
Clean ignition electrode
Ceramic insulator defective
Replace ignition elec-
trode.
Ignition cable defective
Replace ignition cable
Ignition unit defective
Replace ignition unit
Double gas valve does not
open
Cable defective
Check cable, if necessary
replace
Coil defective
Replace coil [ch. 9.13]
Combustion manager does
not detect a flame signal
No ionisation current
present or insufficient
Measure ionisation
current [ch. 7.1.1]
Set ionisation electrode
[ch. 9.5]
Check contact resistance
(terminal, plug)
Correct burner setting
When using an un-
earthed mains supply
(control transformer) the
pole which is to be used
as neutral conductor
must be earthed
Ionisation electrode worn
Replace ionisation elec-
trode
Ionisation cable defective
Replace cable
Flashing 3 times
Air pressure switch fault
Air pressure switch does
not react
Hoses not attached tightly
Check hoses on air pres-
sure switch
Air pressure switch set in-
correctly
Set air pressure switch
[ch. 7.3.2]
Cable defective
Check cable, if necessary
replace
Air pressure switch defect-
ive
Check air pressure
switch, if necessary re-
place
Burner motor does not run
Capacitor defective
Replace capacitor
Cable defective
Check cable, if necessary
replace
Burner motor defective
Check burner motor, if
necessary replace
Flashing 4 times
Flame simulation/
extraneous light
Flame signal prior to or after
operation
Ionisation current present
Extraneous light detection
from 0.8 µA
Find and eliminate per-
turbation
Ionisation electrode defect-
ive
Check the ionisation
electrode, replace if ne-
cessary
Содержание WG20-/1-C LN Series
Страница 1: ...Installation and operating instruction Gas burner WG20 1 C LN 83240802 1 2020 01 ...
Страница 90: ...Installation and operating instruction Gas burner WG20 1 C LN 14 Notes 83240802 1 2020 01 La 90 96 14 Notes ...
Страница 91: ...Installation and operating instruction Gas burner WG20 1 C LN 14 Notes 83240802 1 2020 01 La 91 96 ...
Страница 92: ...Installation and operating instruction Gas burner WG20 1 C LN 14 Notes 83240802 1 2020 01 La 92 96 ...
Страница 95: ...83240802 1 2020 01 La ...