6.5.37 Set maximum DHW load time
To avoid cooling of the heated rooms during DHW loading (DHW priority), the time
for DHW loading can be limited.
If DHW loading is not completed in the time set, the system changes to heating op-
eration for the same period of time and then changes back to DHW operation.
▶
Activate heating engineer level (see Ch. 6.5).
▶
Press function key
DHW
.
✓
Menu
DHW
is displayed.
▶
Use dial knob to move to the second menu level.
▶
Press function key
Max load time DHW
.
✓
Parameter
Max load time WW
is displayed.
▶
Set value using the dial knob and save with function key
OK
.
02
DHW
Legio Fct
Antileg setpoint temp
60.0°C
End
-
+
Max load time DHW
Off
Max load time DHW
604
End
Standard
OK
--; 10min -180min
Off
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
84-106