6.4.2 Adjusting oil side
1. Preset combustion manager
▶
Set fuel selection switch to OIL.
▶
Unplug bridging plug No. 7 on combustion manager.
▶
Switch on voltage supply.
✓
The unprogrammed condition of the combustion manager is indicated by a flashing
display.
The burner goes to lockout.
▶
Press [ENTER] key.
✓
Burner has been reset.
✓
Combustion manager drives to Standby.
Parameters
7
and
8
must be set to value
1
.
▶
Press [Enter] and [+] keys simultaneously for approx. 2 seconds.
✓
The parameter level is activated.
▶
Press [+].
▶
Press [Enter] key until parameter
7
is displayed.
▶
Set parameter
7
(oil pressure switch) to value
1
(activated).
▶
Press [Enter] key.
▶
Set parameter
8
(air pressure switch) to value
1
(activated).
▶
Press [Enter] key until parameter
OFFUPr
is displayed again.
▶
Press [G] and [L/A] simultaneously.
✓
Combustion manager changes to access level.
▶
Press [+].
✓
Setting level (parameter
E0
) is displayed.
▶
Set value
1
(dual fuel burners) using [ENTER] and [+] key.
▶
Press [+].
✓
E1
is displayed.
Installation and operating instruction
Replacing combustion manager W-FM 20 … 24 with W-FM 25
6 Commissioning
83294002 • 2/2014-11 • La
52-70