6.3 Oil burner
1. Preset combustion manager
▶
Unplug bridging plug No. 7 on combustion manager.
▶
Switch on voltage supply.
✓
The unprogrammed condition of the combustion manager is indicated by a flashing
display.
The burner goes to lockout.
▶
Press [ENTER] key.
✓
Burner has been reset.
✓
Combustion manager drives to Standby.
If an oil pressure switch is fitted, set parameters
7
and
8
If an air pressure switch is fitted, set parameter
8
▶
Press [G] and [L/A] simultaneously.
✓
Combustion manager changes to access level.
▶
Press [+].
✓
Setting level (parameter
E0
) is displayed.
▶
Adopt value
0
(single fuel burner), if necessary adjust using [ENTER] and [-] key.
▶
Press [+].
✓
E1
is displayed.
The value of parameter
E1
can not be altered.
▪
0
= intermittent operation (Standard)
▪
1
= continuous operation (only if W-FM 21was used previously)
Installation and operating instruction
Replacing combustion manager W-FM 20 … 24 with W-FM 25
6 Commissioning
83294002 • 2/2014-11 • La
42-70