Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
6 Operation
83054802 1/2018-07 La
88-228
6.9.5 Creating load points, modulating operation
Param & Display
RatioControl
GasSettings
OilSettings
CurveParams
Point
Man
Depending on the load signal, the W-FM controls the actuators in compound in
modulating operation. Each actuator has its own compound curve. The compound
curves are formed from defined load points. 15 load points can be defined for the
compound curves, a minimum of 5 load points are required. On dual fuel burners,
the compound curves for each fuel can be set separately. In menu
Point
1
,
load points can be adjusted or deleted to optimise combustion. In menu
Manual
2
new load points are set.
Point|Load:15.0
|Fuel:10.0
Manual |Air :15.0
|Aux1: 0.0
2
1
During initial commissioning, set load points up to full load. Once full load has been
regulated, optimise combustion in load point 1. Load point 1 must be within the ca-
pacity graph and below below partial load. Now delete all load points between
point 1 and full load. Starting at point 1, set new load points until full load is
achieved. Optimise combustion in the current point before setting a new load point.
To ensure an even speed characteristic curve, the speed of the new load points
should not be altered.
To ensure that control is possible across the entire load range in conjunction with
O
2
trim point 1 must be approx. 50% below partial load (point 2).
0
10
20
30
40
50
60
70
80
90
0
10
20
30
40
50
60
70
80
90
100
0
10
20
30
40
50
60
70
80
90
100
P1
P2 P3
P4
P5
P6
P7
P8
P9
2
1
4
5
6
7
3
1
Burner capacity in %
2
Actuator position in degree of angle
3
Speed in %
4
Fuel
Fuel
5
Air damper
Air
6
Mixing head
Aux1
7
Frequency converter
VSD