6 Operation
83054802 1/2018-07 La
81-228
6.8.7 Continuous running fan
Param & Display
Burner Control
Configuration
ConfigGeneral
ContinuousPurge
If
ContinuousPurge
is activated, the fan runs in each operating phase.
If an air pressure switch is fitted, continuous purge is only possible with a relief
valve at output X4-03 [ch. 3.4.4]. For this, parameter
Start/PS-valve
must be
set to
PS Reli_Inv
in menu
Config Input /Output
.
Setting
Function
deactivated
In phases 00 to 21, output X3-01:1 (fan) is not activated.
In Phase 00 to 21, the frequency converter is controlled
with the idle speed (
HomePosVSD
) set, even if the safety
circuit / burner flange is open.
activated
Output X3-01:1 (fan) and the frequency converter are al-
ways activated, even if the safety circuit / burner flange
are open.
off Sloop
Output X3-01:1 (fan) and the frequency converter are al-
ways activated, except if the safety circuit / burner flange
are open.
deact/VSD-SL
In phases 00 to 21, output X3-01:1 (fan) is not activated.
In Phase 00 to 21, the frequency converter is controlled
with the idle speed (
HomePosVSD
) set, except if the
safety circuit / burner flange is open.
6.8.8 Additional air pressure switch
Param & Display
Burner Control
Configuration
Config input/
output
RotSpeed PS on
RotSpeed PS off
The speed range set is monitored by an additional air pressure switch.
In the OEM level, the additional air pressure switch is deactivated, the function is
not used in standard applications.
Parameters
Function
RotSpeed PS on
The additional air pressure switch must supply an ON sig-
nal above the speed set.
RotSpeed PS off
The additional air pressure switch must supply an OFF
signal below the speed set.