Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
6 Operation
83054802 1/2018-07 La
79-228
6.8.2 Signalling start prevention
Alarm at start prevention
Param & Display
Burner Control
Configuration
ConfigGeneral
AlarmStartPrev
If parameter
AlarmStartPrev
is activated, start prevention is also signalled at
Start prevention in Standby
Param & Display
Burner Control
Configuration
ConfigGeneral
Standby Error
If parameter
Standby error
is activated, faults are also recognised as start
prevention in Standby and are displayed in the ABE.
6.8.3 Normal or direct start
Param & Display
Burner Control
Configuration
ConfigGeneral
NormDirectStart
Start prevention at heat demand during shutdown in phase 78.
Normal start
If
NormalStart
is activated, the fan switches off and the burner only starts after
a home run in phase 10.
Direct start
If
DirectStart
is activated the fan continues to run and the W-FM jumps via
phase 79 to phase 24.
In conjunction with an air pressure switch direct start is only possible with a release
valve at output X4-03 [ch. 3.4.4]. In menu
Config input /output
the para-
meter
Start/PS-valve
must therefore be set to
PS Reli_Inv
.