6 Operation
83054802 1/2018-07 La
76-228
6.7 Manual / Automatic / Off
ManualOperation
SetLoad
Autom/Manual/Off
or
Param & Display
RatioControl
Autom/Manual/Off
Operating mode
Parameter
Autom/Manual/Off
determines the operating mode. In Remote op-
eration the parameter is read only and can not be altered [ch. 6.6.3].
Setting
Function
Automatic
The burner starts if there is a heat demand at in-
put X5-03:1.
The load controller determines the burner capacity.
Manuel
The burner starts if there is a heat demand at input
X5-03:1.
Parameter
SetLoad
determines the burner capacity.
Burner Off
Burner drives to or remains in Standby (Phase 12). A
message, that the W-FM is set to
Burner Off
in
manual operation does not appear.
Target load
Load, to which the burner drives in
Manuel
operating mode.
In modulating operation, the target load can be set within the load limits [ch. 6.9.7].
In multi-stage operation, one of the stages can be selected as the target load.