Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
6 Operation
83054802 1/2018-07 La
58-228
Operation (continued)
O2 module
curr. O2 value
(1
O2 setpoint
(1
Inlet air temperature
(1
Flue gas temperature
(1
CombEfficiency
(1
Burner identification
Operating mode selection
Interface PC
GatewayBASon
GatewayBASoff
Type of Gateway
[Modbus]
O2Ctrl activate
(1
Manual operation
SetLoad
Autom/Manual/Off
[Automatic]
Param & Display
Burner Control
Times
(2
TimeStartup1
MinTimeStartRel
[1 s]
FanRunUpTme
[2 s]
PrepurgeTmeGas
[20 s]
PrepurgeTmeOil
[15 s]
PrepurgeSafeGas
[20 s]
PrepurgeSafeOil
[15 s]
PrepurgePtl1Gas
[0.2 s]
PrpurgePt3Gas
[0.2 s]
PrepurgePt1Oil
[0.2 s]
PrepurgePt3Oil
[0.2 s]
PreIgnTime_Gas
[2 s]
PreIgnTime_Oil
[2 s]
MinOnTime Oil pump
[1 s]
TimeStartup2
Interval1Gas
[2 s]
Interval1Oil
[2 s]
Interval2Gas
[2 s]
Interval2Oil
[2 s]
PressReacTime
[2 s]
TimeShutdown
MaxTmeLowFire
[45 s]
AfterburnTme
[8 s]
PostpurgeT1Gas
[0.2 s]
PostpurgeT1Oil
[0.2 s]
PostpurgeT3Gas
[5 s]
PostpurgeT3Oil
[5 s]
PostpurgeT3long
[0 s]
(1
DelayLackGas
[10 s]
(1
W-FM 200 only
(2
only with HE password