![Weishaupt W-FM 100 Скачать руководство пользователя страница 43](http://html.mh-extra.com/html/weishaupt/w-fm-100/w-fm-100_installation-and-operating-instruction_953373043.webp)
Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
3 Product description
83054802 1/2018-07 La
43-228
O
2
module
Mains voltage / Mains frequency
(120) 230 V / 50 … 60 Hz
Consumption O
2
module
Consumption O
2
sensor
max 4 W
max 90 W
Internal unit fuse
2.5 T, IEC 127-2/1
External fuse
max 16 AB
Type of protection
IP 44
O
2
sensor
Mains voltage / Mains frequency
(120) 230 V / 50 … 60 Hz
Consumption
max 90 W
Type of protection
IP 44
Permissible flue gas velocity
1 … 10 m/s
Flue gas temperature
max 300 °C
Permissible fuels
QGO 20:
Natural and Liquid Petro-
leum Gas
Fuel oil EL
QGO 21:
Natural and Liquid Petro-
leum Gas
Fuel oil EL
Heavy oil to DIN 51603-3
and DIN 51603-5
3.5.2 Ambient conditions
Temperature in operation
–20 … +60 °C
Temperature during transport / storage
–20 … +60 °C
relative humidity
max 95 %, no dew point