Combustion manager W-FM 100 und W-FM 200
6 Operation
83054802 1/2018-07 La
150-228
6.15.7 Operating temperature
Param & Display
Flue Gas Recircula-
tion
OperationTempGas
OperationTempOil
Parameter
OperationTemp …
shows the temperatures that were saved during
temperature compensated commissioning.
The temperature can be displayed at each load point. Invalid values or non-con-
figured operating points are displayed with
XXXX
.
6.15.8 Position limit FGR damper
The position limit restricts the setting of the flue gas damper up and down.
The Position limit is only effective in the temperature compensated operating
modes:
Temp.comp.
TCautoDeact
FGR minimum position
Param & Display
Flue Gas Recircula-
tion
FGR MinPos
Parameter
FGR MinPos
limits the closing angle and ensures a minimum flow.
The minimum position is an absolute value (degree of angle) and applies to the
whole load range.
The FGR damper drives to minimum position if:
the W-FM calculates a smaller closing angles for the temperature compensation
then is defined in
FGR MinPos
,
the operating mode
deactMinpos
or
auto deact
is activated.
Recommended setting: 0°
FGR maximum position
Param & Display
Flue Gas Recircula-
tion
FGR MaxPos Fact
During temperature compensation, parameter
FGR MaxPos Fact
limits the
opening angle upwards [ch. 6.15.6].
The maximum position is set in percent and relates to the current position of the
compound curve (Aux3).
Maximum permissible setting: 10 %