6 Operation
83054802 1/2018-07 La
110-228
6.10.7 O2 sensor
Param & Display
O2 module
Configuration
O2 sensor
Parameter
O2 sensor
activates the O
2
sensor connected.
Setting
Function
no sensor
No O
2
sensor fitted, O
2
trim not possible.
QGO20
QGO 20 fitted, for:
Gas burner
Oil burner (fuel oil EL)
Dual fuel burner (fuel oil EL)
QGO21
QGO 21 fitted, for:
Heavy oil burner (fuel oil MS and S)
Dual fuel burner (fuel oil MS and S)
The O
2
sensor QGO 21 has an increased reaction and settling time. Due to this
behaviour, the release of O
2
trim at burner start has to be delayed for longer. In
conjunction with QGO 21, the factor has to be set to minimum
40
in parameter
NumberTauSuspend
6.10.8 Service interval for O2 sensor
Param & Display
O2 module
Configuration
O2SensServTim
O2SensServTimRes
Setting the service interval
Parameter
O2SensServTim
stipulates the service interval in days for the the O
2
sensor. The interval is deactivated if the setting is "0".
The interval is compared with the total operating hours counter. If the interval has
elapsed, a message appears in the ABE and O
2
trim reacts according to the oper-
O
2
trim is deactivated in operating mode
conAutoDeac
, the O
2
monitor re-
mains activated.
Lockout occurs in operating mode
O2 Alarm
or
O2 controller
.
Reset service interval
Parameter
O2SensServTimRes
resets the service interval.
If O
2
trim is set to
auto deact
, the operating mode has to be reset to
co-
nAutoDeac
.