6 Operation
83054802 1/2018-07 La
109-228
6.10.6 Type of Fuel
Param & Display
O2Ctrl/Limit
GasSettings
OilSettings
Type of Fuel
Fuel user-def
The fuel used must be defined in parameter
Type of Fuel
. If the fuel used is
not available, set parameter
Type of Fuel
to
Fuel user-def
and set the
fuel values in menu
Fuel user-def
.
The type of fuel is used to calculate:
the pre-control
the combustion efficiency
User defined fuel values
The fuel values have to be defined in menu
Fuel user-def
, if parameter
Type of Fuel
is set to
user def
.
V_LNmin
Stoichiometric air requirement (Lambda 1).
[m
3
Air per m
3
Gas or kg Oil].
V_afNmin
Flue gas volume wet in stoichiometric combustion
(Lambda 1).
[m
3
Flue gas wet per m
3
Gas or kg Oil].
V_atrNmin
Flue gas volume dry in stoichiometric combustion
(Lambda 1).
[m
3
Flue gas dry per m
3
Gas or kg Oil].
A2
Fuel factor for the calculation of combustion efficiency.
B/1000
Fuel factor for the calculation of combustion efficiency.
The parameter value corresponds to the resolution
1/1000.
Example: A value of 7 set corresponds to 0.007.