background image

 

 
 
 
 
 
 
 

Installation and Startup Guide

 

This document covers the installation of MT8053iE Series HMI, for the detailed specifications and 
operation, please refer to Brochure and EasyBuilder Pro User Manual. 

Install Environment: 

NEMA Rating

 

MT8053iE Series HMI is NEMA 4 rated (Indoor Only). 

 

Electrical 
Environment

 

MT8053iE Series has been tested to conform to European CE requirements. 
This means that the circuitry is designed to resist the effects of electrical noise. 
This does not guarantee noise immunity in severe cases. Proper wire routing and 
grounding will insure proper operation.

 

Environmental 
Considerations

 

(1)  Make sure that the displays are installed correctly and that the operating 

limits are followed. Avoid installing units in environments where severe 
mechanical vibration or shocks are present. 

(2)  Do not operate the unit in areas subject to explosion hazards due to 

flammable gases, vapors or dusts.

 

(3)  Do not install the unit where acid gas, such as SO2 exists. 
(4)  This device should be mounted in the vertical position and for use on the flat 

surface enclosure.

 

(5)  Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in 

Pollution Degree 2 Environment.

 

(6)  Relative Humidity: 10% ~ 90% (non-condensing)

 

 

Unpacking the Unit

 

Unpack and check the delivery. If damage is found, notify the supplier.   

NOTE: 

Place the operator panel on a stable surface during installation. Dropping it or letting it 

fall may cause damage. 

(1)  Installation Instruction, 2-sided A4 *1 
(2)  Human Machine Interface *1 
(3)  Power Connector *1 
(4)  Brackets & Screws *1 pack 

Installation Instructions 

Use a control box that provides enough stiffness. 
Cutout Dimension: 119 mm x 93 mm. Secure the 
operator panel in position, using all the fastening 
holes and the provided brackets and screws. 
Screw Torque: 2.6 ~ 3.9 lbf.in. (For reaching 
waterproof effect and preventing the panel from 
being deformed.) 
Plan for adequate space around the unit and inside 
the enclosure, for ventilation and cables. Consider 
the heat from other devices inside the enclosure. 
The ambient temperature around the unit must be 
0 ~ 50°C 
Minimum required clearances (along the overlay): 
Top 15 mm / Bottom 50 mm / Sides 15 mm 
Maximum panel thickness: 4.5 mm 

 

Power Connections 

NOTE:   
1. Connect positive DC line to the ‘+’ terminal and the DC 

ground to 

the ‘-’ terminal. 

2. When downloading project using a USB cable, do not 

connect HMI with PLC and PC simultaneously, for electric 

potential difference may result in damage to HMI or PC. 

 

System Settings 

When HMI is powered up and displays image,   
click the system setting button. 
(Default System Password: 111111) 

It is necessary

 to connect the HMI to   

your network through a RJ-45 cable.   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

MT8053iE series 

                                                                                                               

Installation Instruction 

Go to the LAN 1 / LAN 2 tab, you may 
choose to auto get DHCP IP, or 
designate your own IP.

 

 