Installation and Startup Guide
This document covers the installation of MT8053iE Series HMI, for the detailed specifications and
operation, please refer to Brochure and EasyBuilder Pro User Manual.
Install Environment:
NEMA Rating
MT8053iE Series HMI is NEMA 4 rated (Indoor Only).
Electrical
Environment
MT8053iE Series has been tested to conform to European CE requirements.
This means that the circuitry is designed to resist the effects of electrical noise.
This does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.
Environmental
Considerations
(1) Make sure that the displays are installed correctly and that the operating
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2) Do not operate the unit in areas subject to explosion hazards due to
flammable gases, vapors or dusts.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in
Pollution Degree 2 Environment.
(6) Relative Humidity: 10% ~ 90% (non-condensing)
Unpacking the Unit
Unpack and check the delivery. If damage is found, notify the supplier.
NOTE:
Place the operator panel on a stable surface during installation. Dropping it or letting it
fall may cause damage.
(1) Installation Instruction, 2-sided A4 *1
(2) Human Machine Interface *1
(3) Power Connector *1
(4) Brackets & Screws *1 pack
Installation Instructions
Use a control box that provides enough stiffness.
Cutout Dimension: 119 mm x 93 mm. Secure the
operator panel in position, using all the fastening
holes and the provided brackets and screws.
Screw Torque: 2.6 ~ 3.9 lbf.in. (For reaching
waterproof effect and preventing the panel from
being deformed.)
Plan for adequate space around the unit and inside
the enclosure, for ventilation and cables. Consider
the heat from other devices inside the enclosure.
The ambient temperature around the unit must be
0 ~ 50°C
Minimum required clearances (along the overlay):
Top 15 mm / Bottom 50 mm / Sides 15 mm
Maximum panel thickness: 4.5 mm
Power Connections
NOTE:
1. Connect positive DC line to the ‘+’ terminal and the DC
ground to
the ‘-’ terminal.
2. When downloading project using a USB cable, do not
connect HMI with PLC and PC simultaneously, for electric
potential difference may result in damage to HMI or PC.
System Settings
When HMI is powered up and displays image,
click the system setting button.
(Default System Password: 111111)
It is necessary
to connect the HMI to
your network through a RJ-45 cable.
MT8053iE series
Installation Instruction
Go to the LAN 1 / LAN 2 tab, you may
choose to auto get DHCP IP, or
designate your own IP.
3
5
4
1
2