![weintek iR-ETN Скачать руководство пользователя страница 11](http://html.mh-extra.com/html/weintek/ir-etn/ir-etn_user-manual_953138011.webp)
iR-ETN User Manual
8
…..
…..
…..
…..
…..
6164
1814
Read/Write
1word
Digital Output Error Value (bit511-495)
6165
1815
Read/Write
1word
Analog Output Error Mode
(channel 15-0)
0:Keep last value
1:Error value
6166
1816
Read/Write
1word
Analog Output Error Mode
(channel 31-16)
6167
1817
Read/Write
1word
Analog Output Error Mode
(channel 47-32)
6168
1818
Read/Write
1word
Analog Output Error Mode
(channel 63-48)
6169~
6232
1819~
1858
Read/Write
64word
Analog Output Error Value
(channel 63-0)
-32768~32768
The Default Value
7.11
Address
Read/Write
Data size
Description
Default
Dec
Hex
3008-
3023
0BC0-
0BCF
Read/Write
16word
Product name
“iR-ETN”
5100~
5612
13EC~
15EC
Read/Write
512word
Setting the time filter
(Digital input 0-511)
0
6100
17D4
Read/Write
1word
Life Guarding Time
0
6101-
6132
17D4-
17F4
Read/Write
32 word
Digital Output Error Mode
0xFF
6133-
6164
17F5-
1814
Read/Write
32 word
Digital Output Error Value
0
6165-
6168
1815-
1818
Read/Write
4word
Analog Output Error Mode
0xFF
6169-
6232
1819~
1858
Read/Write
64word
Analog Output Error Value
0
※
After pressing [Reset] button, the Default Value will be filled into corresponding
registers.
Device Error Code List
7.12
Refer to special register address 5000/1388H
Bit Number
Description
Bit0
Low power alarm
Bit1
iBus initialization fault
Bit2
Hardware error
Bit3
Module lost connection
Bit4
Module alarm
Bit5
Number of iBus exceeds 16
Bit6
Power consumption exceeded at iBus system
Bit7~15