![weintek iR-ETN Скачать руководство пользователя страница 10](http://html.mh-extra.com/html/weintek/ir-etn/ir-etn_user-manual_953138010.webp)
iR-ETN User Manual
7
Product Code List
7.8
Item
Product
Code
1
iR-DI16-K
0154h
2
iR-DM16-P
0351h
3
iR-DQ16-P
0251h
4
iR-DM16-N
0352h
5
iR-DQ16-N
0252h
6
iR-DQ08-R
0243h
7
iR-AQ04-VI
0525h
8
iR-AI04-VI
0425h
9
iR-AM06-VI
0635h
10
iR-AI04-TR
0426h
11
iR-COP
0701h
12
iR-ETN
0702h
13
iR-PU01-P
0819h
Special Register
7.9
Address
Read/Write
Data size
Description
Dec
Hex
1013
03F5
Read/Write 1word
Indicator Mode:
0: Modbus TCP
1: EtherNet IP
5000
1388
Read
1word
Device Error code
5001
1389
Read
1word
Reserved
5002
138A
Read
1word
Slot1~16 of Module disconnect
5100~
5612
13EC~
15EC
Read/Write
512word
Setting the time filter (digital input, unit: ms). The
time filter is disabled when it is set to less than 5ms.
The time filter remains at 1000ms when it is set to
longer than 1000ms. (digital input 0-511)
6000
1770
Write
1word
Device Command
0x5269
:
Reset iBus
0x5250
:
Parameter to default without TCP/IP
0x5257
:
Device Reset Warm
Life Guarding Register
7.10
If the communication was missing for longer than the Life Guarding Time, a Life
Guard Event is indicated. The output behavior is determined by whether Error Mode
is enabled or disabled. Enabling Error Mode will output an Error Value when an event
occurs. Disabling Error Mode will keep the last value (for both digital and analog).
Address
Read/Write
Data size
Description
Dec
Hex
6100
17D4
Read/Write
1word
Life Guarding Time, unit: ms, 0: Disabled
6101
17D5
Read/Write
1word
Digital Output Error Mode (bit15-0)
0:Keep last value
1:Error value
6102
17D6
Read/Write
1word
Digital Output Error Mode (bit31-16)
…..
…..
…..
…..
…..
6132
17F4
Read/Write
1word
Digital Output Error Mode (bit511-495)
6133
17F5
Read/Write
1word
Digital Output Error Value (bit15-0)
0:Low
1:High
6134
17F6
Read/Write
1word
Digital Output Error Value (bit31-16)