Installation and Startup Guide

 

This document covers the installation of cMT-SVRX Series, for the detailed specifications and operation, 
please refer to Datasheet, Brochure and EasyBuilder Pro User Manual. Please read all warnings, 
precautions, and instructions on the device carefully before use. 

Install Environment: 

Electrical 
Environment

 

The HMI product has been tested to conform to European CE requirements. This 
means that the circuitry is designed to resist the effects of electrical noise. This 
does not guarantee noise immunity in severe cases. Proper wire routing and 
grounding will insure proper operation.

 

Environmental 
Considerations

 

(1)  Make sure that the units are installed correctly and that the operating limits 

are followed. Avoid installing units in environments where severe 
mechanical vibration or shocks are present. 

(2)  Do not operate the unit in areas subject to explosion hazards due to 

flammable gases, vapors or dusts.

 

(3)  Do not install the unit where acid gas, such as SO2 exists. 
(4)  This device should be mounted in the vertical position and for use on the flat 

surface enclosure.

 

(5)  For use in Pollution Degree 2 Environment and dry location.

 

(6)  Relative Humidity: 10% ~ 90% (non-condensing)

 

Cleaning 
Considerations 

Clean the device using dry cloths. Do not use liquid or spray detergents for 
cleaning. 

IP rating 

IP 20 

 
Warning 

Protection impairment if used in a manner not specified by the manufacturer. 
Déficit de protection si utilisé d'une manière non spécifiée par le fabricant. 

 

Unpacking the Unit

 

Unpack and check the delivery. If damage is found, notify the supplier.   

NOTE: Place the unit on a stable surface during installation. Dropping it or letting it fall may cause 

damage. 

(1) Installation Instruction, A4 double sided *1 
(2) Power Connector *1 
(3) cMT-SVRX *1 

 

Installation Instructions 

Rail mounting: DIN rail 35mm 
Panel mounting: Use two M4 or #8 panhead screws, mounting hole size is 4.6mm 
Plan for adequate space around the unit and inside the enclosure, for ventilation and cables. Consider the 
heat from other devices inside the enclosure. The ambient temperature around the unit must be 0 ~ 50°C. 
The aluminum flat-sheet at the back of the unit is a heat sink. Please be careful not to touch the heat sink 
since its heat can rise to 70°C in maximum when the unit is running. Planning for a 3cm space between the 
unit and other devices is recommended. 

 

Power Connections 

 

Power Connector Specifications:   
Wire AWG: 24~12 
Wiring Conductor Minimum Temperature: 75°C 
Screw Torque: 4.5 lbf-in (max.) 
Copper conduct only. 
 
Spécifications du connecteur d'alimentation: 
AWG de fil: 24 ~ 12 
Température minimale du conducteur de câblage: 75°C 
Couple de vis: 4.5 lbf-in (max.) 
Conducteur en cuivre seulement 

 

 

NOTE: Connect positive DC line to the ‘+’ terminal and the DC 
ground to the ‘-’ terminal.

 

 

System Settings 

Connect cMT-SVRX with a router using a RJ-45 cable, launch EasyBuilder Pro on your computer, open 
Download window to find this cMT-SVRX.   
 
After connecting cMT-SVRX successfully, enter the IP address of this cMT-SVRX in the browser to open 
the System Settings page, and then enter 

the default password “111111” to log in and configure cMT-SVRX. 

 

 

 

 

 

 

 

 