7 Planning IO-Link device configurations
| Editing IO-Link device configurations online
45
Manual Communication module UR20-4COM-IO-LINK
2547720000/03/09.2019
Finding and rectifying parameter errors
Faulty parameterised IO-Link devices are indicated by a red
frame around the IO-Link port concerned.
Faulty parameterised IO-Link device
▶
Open the
detailed view
of the IO-Link device.
Jumping to the faulty parameter entry
▶
Click
Scroll to error
in order to jump to the next faulty
parameter entry.
The faulty entry is indicated by a red frame. A note regarding
error diagnosis is displayed.
Faulty parameter entry
▶
Correct the faulty entry.
▶
Repeat the procedure until all errors have been rectified.
7.5
Editing IO-Link device configurations online
WARNING!
Manipulation of the control unit!
During commissioning, the system may be
manipulated to such an extent that this can
result in risks to life and material damage.
▶
Make sure that system components can-
not start up unintentionally!
Connecting to the fieldbus coupler
The u-remote station must be completely assembled and
supplied with voltage. The computer must be connected to
the u-remote station via USB or Ethernet.
If you access a fieldbus coupler via the
u-remote IO-Link configurator and the u-remote
web server simultaneously, this may result in ac-
cess conflicts.
▶
Click
Connect
on the
starting page
. Alternatively, you
can click
Connect
in the
menu bar
.
▶
Enter the IP address of the fieldbus coupler.
▶
Click
OK
.
▶
You may be requested to enter your user name and pass-
word.
You need the same user name and the same password that
you use when logging in for the u-remote web server of this
fieldbus coupler.
The following login data applies on delivery:
user name:
admin
password:
Detmold
▶
Enter the user name and password.
The online mode of the IO-Link Configurator is started. The
fieldbus coupler with connected UR20-4COM-IO-LINK mod
-
ules is displayed in the device tree.
▶
Click in the
device tree
on the IO-Link master whose
configuration you want to edit.
The IO-Link port overview of the IO-Link master is displayed.
Содержание UR20 Series
Страница 1: ...Remote I O System u remote UR20 Communication module UR20 4COM IO LINK Manual Let s connect...
Страница 8: ...8 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 10: ...10 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 20: ...20 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 48: ...48 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 54: ...54 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...