Installation, operation and maintenance manual – Squirrel cage motor – WGM20 Line                                                 14108242

 

5

 

STARTING 

 

5.1

 

DIRECT ON-LINE STARTING 

 
It is the simplest and most economically feasible method; 
however, it must only be used when the starting current 
does not affect the power grid.  
Bear in mind that the starting current of motors may reach 
6 to 7 times the rated current value. Therefore, it must be 
ensured that this current (Ip) will not affect the supply of 
other consumers because of the high voltage drop in the 
power grid.  
This requirement is met in one of the three situations: 
a)

 

When the power grid is 

"strong"

 enough and the 

motor current is negligible in relation to the grid 
capacity. 

b)

 

The motor is always started without load, which 
reduces the starting time and, in turn, the duration of 
the starting current and the momentary voltage drop, 
which is acceptable for the other consumers of the 
grid; 

c)

 

When DOL starting is duly authorized by the local 
electric utility company. 

When the motor starting current is high, the following 
detrimental consequences may occur: 
a)

 

The high voltage drop in the power supply system may 
cause interference in equipment installed in this 
system; 

b)

 

The protection system (cables, contactors) must be 
oversized, increasing the installation costs.  

 

 

NOTE 

In some cases, there is an imposition of the 
electric utility companies that limits the 
voltage drop of the grid. 

 

5.2

 

DIRECT ONLINE STARTING 
FREQUENCY 

 
Since induction motors have a high starting current, the 
time spent to accelerate loads with high inertia results in a 
quick rise of the motor temperature. If the intervals 
between successive starts are too short, the temperature 
of the windings will rise quickly, reducing their useful life or 
even burning them. The NBR 17094 and IEC60034-1 
standards establishes a minimum starting duty to which 
the motors must be able to comply: 
a)

 

Two successive starts: the first one with the motor 
cold, i.e., with its windings at ambient temperature, 
and the second one right afterwards, but only after 
the motor has decelerated to a full stop; 

b)

 

One start with the motor hot, i.e., with the windings at 
continuous duty temperature. 

The first condition simulates the case in which the first 
motor start is aborted, for instance, by the trip of the 
motor protection, when a second motor start is permitted 
right afterwards.   
The second condition simulates the case of an accidental 
motor shutdown under normal operation, for instance, by 
power outage, when the motor restart is allowed right after 
the power is reestablished. 
 

 

NOTE 

Special starting conditions must be checked 
in the specific motor documentation  before 
starting the procedure.

 

 

5.3

 

LOCKED ROTOR CURRENT 

 
The motor nameplate indicates the value of I

P

/I

n

, which is 

the relation between the starting current and the rated 
current of the motor. 
 

5.4

 

STARTING WITH REDUCED 
CURRENT 

 
If direct online starting is not possible, the following 
starting systems can be used in order to reduce the motor 
starting current. 

 

Star-delta starter; 

 

Series-parallel starter; 

 

Autotransformer starter; 

 

Static starter or soft-starter; 

 

Frequency inverter. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание WGM20 Series

Страница 1: ...utomation I Energy I Transmission Distribution I Coatings Three phase induction motors cooled by water jacket WGM20 line Squirrel cage rotor Horizontal and Vertical Installation Operation and Maintena...

Страница 2: ......

Страница 3: ...Installation Operation and Maintenance Manual Document Number 10005256831 Material number 14108242 Model WGM20 Language English Revision 01 March 2018...

Страница 4: ......

Страница 5: ...efore we recommend that you read this manual carefully before proceeding with the installation operation or maintenance of the motor in order to ensure safe and reliable operation of your equipment an...

Страница 6: ......

Страница 7: ...17 3 3 3 6 Bearings 17 3 3 3 7 Terminal boxes 17 3 3 3 8 Cleanliness and conservation of the motor during storage 17 3 3 3 9 Inspections and records during storage 17 3 3 3 10 Predictive preventive m...

Страница 8: ...ng 28 4 8 8 Couplings 28 4 8 8 1 Direct coupling 28 4 8 8 2 Gear coupling 28 4 8 8 3 Belt drive 28 5 STARTING 30 5 1 DIRECT ON LINE STARTING 30 5 2 DIRECT ONLINE STARTING FREQUENCY 30 5 3 LOCKED ROTOR...

Страница 9: ...assembly 40 7 10 9 4 NDE vertical bearing disassembly 40 7 10 9 5 Bearing assembly 41 7 10 9 6 Bearing insulation 41 7 10 10Rolling bearing replacement 41 7 10 11Bearing protection 41 7 10 11 1 Protec...

Страница 10: ......

Страница 11: ...s with major special features is necessary consult WEG All procedures and standards contained in this manual must be observed in order to ensure proper operation of the motor and the safety of the per...

Страница 12: ...n for example keep people away avoid contact of children etc Those responsible for the safety of the installation must ensure that Only qualified personnel install and operate the equipment They have...

Страница 13: ...ls within the limits in accordance with the IEC60034 1 standard Voltage may vary within a range of 10 of the rated value Frequency may vary within a range of 5 to 3 of the rated value Figure 2 1 Volta...

Страница 14: ...the final assembly A complete visual inspection of the motor must be carried out after removing the package The shaft locking system must be removed just before the installation and stored to be used...

Страница 15: ...heaters must remain powered during storage in order to avoid moisture condensation inside the motor Any damage to the paint or corrosion protection of the machined parts must be repaired 3 3 1 Outdoor...

Страница 16: ...tation and fungus formation the package must be protected in the storage place by spraying it or painting it with appropriate chemicals The package preparation must be prepared carefully by an experie...

Страница 17: ...erminal boxes must also be inspected observing the following aspects The inside must be dry clean and free of any dust accumulation The contact elements cannot present corrosion The seals must be in p...

Страница 18: ...inal boxes X X Inspect the seals and gaskets X X BEARINGS Rotate the shaft X Relubricate the bearing X Disassemble and clean the bearing If the storage period exceeds 2 years 3 3 4 Preparation for com...

Страница 19: ...operation it must be protected against moisture high temperatures and dirt thus avoiding impacts on the insulation resistance The winding insulation resistance must be measured before putting the moto...

Страница 20: ...n index allows the assessment of the motor insulation conditions DANGER In order to avoid accidents the winding must be grounded immediately after measuring the insulation resistance 4 4 6 Conversion...

Страница 21: ...ure the working conditions are considered special and the motor specific documentation must be consulted The Table 4 4 shows the numerical values and the composition of the acceptable temperature at t...

Страница 22: ...connecting cables must be shielded and the shield must be grounded The installation of the signal cables should be done in a linear manner avoiding turns and should not be installed near of the power...

Страница 23: ...32 148 70 149 07 149 45 130 149 82 150 20 150 57 150 95 151 33 151 70 152 08 152 45 152 83 153 20 140 153 58 153 95 154 32 154 70 155 07 155 45 155 82 156 19 156 57 156 94 150 157 31 157 69 158 06 158...

Страница 24: ...motor cooling system nameplate must be strictly followed The water inlets and outlets must not be obstructed because it can cause overheating or even lead to burning the motor 4 6 1 1 Cooling system...

Страница 25: ...x with the cover 3 NOTE The stator terminal box allows for 180 rotation in horizontal motors and 90 in vertical motors Figure 4 5 Stator terminal box Figure 4 5 legend 1 Stator terminal box 2 Connecti...

Страница 26: ...ust be tightened The rail closer to the driving pulley must be mounted so that the positioning bolt is placed between the motor and the driven machine The other rail must be mounted with the bolt in t...

Страница 27: ...rregularities on the dial gauge tip Choosing the upper vertical point as 0 half of the difference between the dial gauge measurements at the 0 and 180 points represents the vertical coaxial error In c...

Страница 28: ...or removed with the aid of proper devices and never by means of rudimentary tools such as hammers sledgehammers etc ATTENTION Dowel pins nuts washers and leveling shims may be supplied with the motor...

Страница 29: ...evented by applying a resin like material such as pitch for instance The belt tension must be just enough to prevent slippage during operation NOTE Belts too tensioned increase the load on the shaft e...

Страница 30: ...uction motors have a high starting current the time spent to accelerate loads with high inertia results in a quick rise of the motor temperature If the intervals between successive starts are too shor...

Страница 31: ...the space heaters 2 Set the protections in the control panel 3 Turn ON the water cooling system checking the necessary flow and pressure and the temperature of the cooling water 4 Rotate the motor sh...

Страница 32: ...when the purchase contract specifies different values The vibration measurements are carried out on the NDE and DE bearings in the vertical horizontal and axial directions When the customer sends the...

Страница 33: ...ance measurements must be done at regular intervals especially during humid weather and after prolonged motor stoppages Low values or sudden variations in the insulation resistance must be investigate...

Страница 34: ...r an increase in cooling water temperature it indicates an increase of scale formation in the channels which over time can clog and impair the water circulation In this case the cooling water channels...

Страница 35: ...or Table 8 2 and locked with chemical lock 7 6 VIBRATION Any evidence of increase in the unbalance or vibration of the motor must be investigated immediately 7 7 MOTOR OUT OF OPERATION When the motor...

Страница 36: ...o make the lubrication with the motor in operation in order to ensure the renewal of the grease in the rolling bearing housing If that is not possible due to the presence of rotating parts near the gr...

Страница 37: ...es for regular applications Manufacturer Grease Constant operating temperature C Multiplication factor Exxon Mobil UNIREX N3 Lithium Complex Soap 30 to 150 0 90 Shell ALVANIA RL3 Lithium Soap 30 to 12...

Страница 38: ...perties of the mixture are within the property ranges of the greases individually In general greases with the same type of soap are compatible however depending on the proportion of the mixture there...

Страница 39: ...rew 7 that fasten the grease flinger 5 Remove the grease flinger 4 6 Remove the DE end shield of the motor 2 7 Remove the bearing 3 8 Remove the internal bearing cap 6 if is necessary 7 10 9 2 NDE hor...

Страница 40: ...the bearing 3 8 Remove the internal bearing cap 5 if is necessary 7 10 9 4 NDE vertical bearing disassembly Figure 7 9 NDE vertical bearing Figure 7 9 legend 1 Shaft 2 NDE end shield 3 Bearing 4 Grea...

Страница 41: ...tions in the reverse order Figure 7 10 External bearing cap 7 10 9 6 Bearing insulation The motor has insulated NDE end shield and shaft grounding brush to prevent the passage of electric current thro...

Страница 42: ...hreaded connection cable 1 Motor accessory 2 Accessory connection cable Accessory location Accessory disassembly assembly Pt 100 of water inlet and outlet Water leakage sensor Horizontal Motors Water...

Страница 43: ...and coil heads support the shaft on DE and NDE sides 8 1 1 Disassembly 1 Disconnect the cables of the bearings temperature sensors in the accessories terminal box 2 Disassemble the DE bearing 6 and th...

Страница 44: ...rminal box 2 Disassemble the DE bearing 6 and the motor DE end shield 4 as described in item 7 10 9 3 3 Remove the KMT nut 16 that fasten the NDE bearing 4 Disassemble the NDE bearing 8 and the motor...

Страница 45: ...3 510 338 382 254 M30 3 5 693 461 520 346 M33 3 5 937 622 703 466 M36 4 1207 802 905 602 M42 4 5 1929 1280 1447 960 M48 5 2892 1918 2170 1440 NOTE The resistance class is normally indicated on the hea...

Страница 46: ...tions x BEARINGS Control of noise vibration leaks and temperature x Lubricant quality control x Lubricant change According to the period indicated on the bearing nameplate COOLING SYSTEM Verification...

Страница 47: ...the power cables The stator current oscillates under load with double the slip frequency The motor presents a humming noise during starting Rotor winding is interrupted Check and repair the rotor win...

Страница 48: ...ose Retighten and lock the screws The rotor balancing conditions become worse after the assembly of the coupling Balance the coupling Resonance in the foundation Adjust the foundation Motor frame defo...

Страница 49: ...www weg net 14108242 Installation operation and maintenance manual Squirrel cage motor WGM20 Line l 49 12 DECLARATION OF CONFORMITY...

Страница 50: ...nty in connection with this sale and is in lieu of all other warranties expressed or implied written or oral There are no implied warranties of merchantability or fitness for a particular purpose that...

Страница 51: ...remona Phone 39 374 340 404 www ferrarisrl it STIAVELLI IRIO S P A Via Pantano Blocco 16 Capalle 50010 Campi Bisenzio FI Phone 39 55 898 448 www stiavelli com JAPAN WEG ELECTRIC MOTORS JAPAN CO LTD Yo...

Отзывы: