RUW-01 | 13
- English -
CANopen Remote Unit
Table 4:
Remote unit error indication
Status
ERROR LED
Description
Without ERROR
Off
The device is in normal operational conditions, on-line
and with established connections
Warning
Flashing red,
once every
second
It indicates that the CAN controller is in Warning or
Error Passive status
It may occur, for instance, if it is the only equipment
connected to the CANopen network
Node Guarding
or Heartbeat
Error
Flashing red,
twice every
second
The CANopen communication error control has
detected a communication error by using the Node
Guarding or Heartbeat Error mechanisms
BUS OFF error
Constant red
It indicates that the CAN controller is in the BUS OFF
status
It indicates a critical operational condition in the
CANopen network, normally associated to installation
problems or incorrect baud rate configuration
It is necessary to cycle the power of the RUW-01
BUS POWER
OFF error
Constant red
It indicates that the CAN interface does not have power
supply between the poles 1 and 5 of the connector
CANopen
has not been
initialized
Flashing red
every 50 ms
It indicates that the CANopen protocol has not been
initialized. Verify if the address has been adjusted in a
valid value (01h-7Fh)
6.2 DIAGNOSIS OF THE DIGITAL INPUTS AND OUTPUTS
Table 5:
Status indication of the digital inputs and outputs
Status
I/O LED
Description
Output is On
(RUW-01.00 only)
Red
The correspondent output is on
Output is Off
(RUW-01.00 only)
Off
The correspondent output is off
Activated Input
Green
The correspondent input is activated
Deactivated Input
Off
The correspondent input is deactivated