DIAGNOSTICS AND TROUBLESHOOTING
Fault/alarm
Reset
Possible causes
A0366
Fault in the temperature sensor of
the thermal protection relay CH7
Power-on.
Manual (
O
/RESET key).
Auto-reset.
It resets automatically after the cause is
eliminated.
DIx.
Networks.
Temperature sensor broken wire.
PT100 accessory connectors disconnected.
Temperature channel active without a sensor
connected to the PT100 accessory.
A0367
Fault in the temperature sensor of
the thermal protection relay CH8
Power-on.
Manual (
O
/RESET key).
Auto-reset.
It resets automatically after the cause is
eliminated.
DIx.
Networks.
Temperature sensor broken wire.
PT100 accessory connectors disconnected.
Temperature channel active without a sensor
connected to the PT100 accessory.
F0368
Overtemperature detected by the
thermal protection relay CH1
Power-on.
Manual (
O
/RESET key).
Auto-reset.
DIx.
Networks.
Temperature above the fault level set on the ther-
mal protection relay and P0315 > 0.
F0369
Overtemperature detected by the
thermal protection relay CH2
Power-on.
Manual (
O
/RESET key).
Auto-reset.
DIx.
Networks.
Temperature above the fault level set on the ther-
mal protection relay and P0315 > 0.
F0370
Overtemperature detected by the
thermal protection relay CH3
Power-on.
Manual (
O
/RESET key).
Auto-reset.
DIx.
Networks.
Temperature above the fault level set on the ther-
mal protection relay and P0315 > 0.
F0371
Overtemperature detected by the
thermal protection relay CH4
Power-on.
Manual (
O
/RESET key).
Auto-reset.
DIx.
Networks.
Temperature above the fault level set on the ther-
mal protection relay and P0315 > 0.
F0372
Overtemperature detected by the
thermal protection relay CH5
Power-on.
Manual (
O
/RESET key).
Auto-reset.
DIx.
Networks.
Temperature above the fault level set on the ther-
mal protection relay and P0315 > 0.
F0373
Overtemperature detected by the
thermal protection relay CH6
Power-on.
Manual (
O
/RESET key).
Auto-reset.
DIx.
Networks.
Temperature above the fault level set on the ther-
mal protection relay and P0315 > 0.
F0374
Overtemperature detected by the
thermal protection relay CH7
Power-on.
Manual (
O
/RESET key).
Auto-reset.
DIx.
Networks.
Temperature above the fault level set on the ther-
mal protection relay and P0315 > 0.
F0375
Overtemperature detected by the
thermal protection relay CH8
Power-on.
Manual (
O
/RESET key).
Auto-reset.
DIx.
Networks.
Temperature above the fault level set on the ther-
mal protection relay and P0315 > 0.
MVW3000 | 7-10
Содержание MVW3000 Series
Страница 2: ......
Страница 58: ...1 QUICK REFERENCE OF PARAMETERS AND FAULTS MVW3000 1 52...
Страница 62: ...2 SAFETY INSTRUCTIONS MVW3000 2 4...
Страница 192: ...6 SPECIAL FUNCTIONS MVW3000 6 4...
Страница 262: ...7 DIAGNOSTICS AND TROUBLESHOOTING MVW3000 7 70...
Страница 263: ......