5
DETAILED PARAMETER DESCRIPTION
Motor current (P0003)
Overload current
I(A)
Time (s)
4
3
2.5
2
1.5
1.1
1.3
0.5
0
0 15 30
60 75
100
150
300
t = 30
I-1
Figure 5.18:
Function I x t - overload detection
Curve for motor with independent ventilation
Curve for self-ventilated motor
P0156
0
10
20
30
40
50
60
70
80
90
100
110
0
10 20 30 40 50 60 70 80 90 100 110 120 130 140
Rated speed (%)
P040
1 (Motor rated
curr
ent) (%)
P0157
P0158
P0158
P0156
P0157
Figure 5.19:
Overload protection levels
✓
NOTE!
When P0295 or P0401 are changed, the values of P0156 to P0158 are changed according to the
new current:
P0156 = 1.10
×
P0157 = 0.90
×
P0158 = 0.50
×
P0159 - Temperature alarm I x t
Adjustable range:
0 to 100 %
Factory setting:
80 %
Acesso:
Menu
→
Configurations
→
Protections
Description:
When the value of P0076 reaches the value given in this parameter, alarm A0046 (Motor Ixt function overload)
is indicated on the HMI.
MVW3000 | 5-25