CONNECTING A DEVICE TO THE DRIVE SCAN
Table 5.2:
Parameters related to the RS485-01, CAN/RS485-01 and RS485-05 accessories
Parâmetro
Descrição
Faixa de valores
P0316
Serial interface status
0 = Inactive
1 = Active
2 = Watchdog error
Table 5.3:
Parâmetros relacionados aos acessórios PLC11-01 e PLC11-02
Parameter
Description
Values range
P1280
Serial protocol
1 = Modbus RTU (Slave)
P1281
Serial address
1 a 247
P1282
Serial baud rate
0 = 1200 bps
1 = 2400 bps
2 = 4800 bps
3 = 9600 bps
4 = 19200 bps
5 = 38400 bps
P1283
Serial communication configuration
0 = 8 bits, no parity, 1 stop bit
1 = 8 bits, even parity, 1 stop bit
2 = 8 bits, odd parity, 1 stop bit
3 = 8 bits, no parity, 2 stop bits
4 = 8 bits, even parity, 2 stop bits
5 = 8 bits, odd parity, 2 stop bits
P1284
Serial Watchdog
0,0 a 999,0 s
Figure 5.4illustrates an RS-485 network among the CFW11 inverters, using all communication modules.
Drive Scan
RS485
1
2
3
CFW-11
4
RS485-01
A- B+
GND
CAN/RS485-01
PLC11
A- B+
RS485-05
A- B+
GND
Cabo
2 3
A- B+
GND
2 3
2
8 9 5
Figure 5.3:
RS-485 network among several CFW11 and one Drive Scan
Note that the RS-485 signals (positive, negative and ground) of each inverter must share the same point or node.
For example, the negative signals (A-) of inverters 1, 2, 3 and 4 must be connected to the same node. The same
must be true for the positive (B+) and GND (if any) signals. It is important to remember that inverters in an RS-485
network must have different serial addresses.
5.2.2
ETHERNET
To connect to the WCD-ED300 via Ethernet GbE1 communication interface using the Modbus TCP protocol, it is
necessary to install on the CFW11 one of the accessories listed in
Table 5.4
. It is also important to observe the
following settings in the table:
Low Voltage Devices | 5-3
Содержание Drive Scan
Страница 2: ......
Страница 4: ...Summary of reviews Version Revision Description 1 0X 00 First edition...
Страница 11: ...2 INSTALLATION RECOMMENDATIONS Low Voltage Devices 2 2...
Страница 58: ...6 SETTING THE DRIVE SCAN ON THE MFM Figure 6 22 RS 485 network con guration Low Voltage Devices 6 13...
Страница 59: ...6 SETTING THE DRIVE SCAN ON THE MFM Low Voltage Devices 6 14...
Страница 71: ...8 SETTING THE IP ON WINDOWS 10 Click on OK Figure A 7 Figure A 7 Changing IP Low Voltage Devices 8 3...
Страница 72: ......
Страница 73: ......