Vector Control
11
CFW700 | 11-29
Seq.
Action/Result
Display Indication
1
-
Monitoring Mode.
-
Press
ENTER/MENU
key to go to
the 1
st
level of the programming
mode.
2
-
The
PARAM
group is selected,
press the
or
keys to select
the
STARTUP
group.
3
-
Press
ENTER/MENU
when the
group is selected.
4
-
The parameter
“P0317 - Oriented
Start-up”
is then selected, press
the
ENTER/MENU
to get into the
parameter content.
5
-
Change the parameter P0317 to
“1 - Yes”
, by using the
key.
6
-
Press
ENTER/MENU
to save.
7
-
In this moment the Oriented Start-up
routine is initiated and the
“CONF”
status is indicated at the keypad
(HMI).
-
The parameter
“P0000 - Access to
Parameters”
is selected. Change
the password to set the remaining
parameters if necessary.
-
Press the
key to the next
parameter.
8
-
- If necessary, change
“P0296 -
Line Rated Voltage”.
This change
will affect P0151, P0153, P0185,
P0321, P0322, P0323 and P0400.
-
Press the
key to the next
parameter.
Seq.
Action/Result
Display Indication
9
-
If necessary, change
“P0298 -
Application”
parameter. This
change will affect P0156, P0157,
P0158, P0401, P0404 and P0410
(P0410 only will affect if P0202 = 0,
1, 2 or 3). The time and level of the
IGBT overload protection will also
be affected.
-
Press the
key to the next
parameter.
10
-
Set parameter
“P0202 -
Type of Control”
pressing
“ENTER/MENU”
. Press the
key to select the desired
option:
“[4]=Sensorless”
or
“[5]=Encoder”
. This change
resets P0410. Then, press
“ENTER/MENU”
.
-
There are three options to exit the
oriented start-up:
1 - Running the Self-tunning;
2 - Manual settings of parameters
from P0409 to P0413;
3 - Changing P0202 from vector to
scalar control.
-
Press the
key to the next
parameter.
11
-
If necessary, change
“P0398
- Motor Service Factor”
parameter. This change will
affect the current and the time
of the motor overload protection
operation.
-
Press the
key to the next
parameter.
12
-
If necessary, change
“P0400 -
Motor Rated Voltage”
parameter.
-
This change corrects the output
voltage by the factor
“x = P0400/P0296”.
-
Press the
key to the next
parameter.
13
-
If necessary, change
“P0401 -
Motor Rated Current”
parameter.
This change will affect P0156,
P0157, P0158 and P0410.
-
Press the
key to the next
parameter.
Figure 11.5:
Vector mode Oriented Start-up
Содержание CFW700
Страница 2: ......
Страница 4: ......
Страница 8: ...Summary...
Страница 34: ...2 General Information 2 4 CFW700...
Страница 38: ...3 About the CFW700 3 4 CFW700...
Страница 56: ...7 Starting up and Settings 7 4 CFW700...
Страница 58: ...8 Available Control Types 8 2 CFW700...
Страница 78: ...10 VVW Control 10 8 CFW700...
Страница 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...
Страница 184: ...16 Read only Parameters 16 12 CFW700...