VVW Vector Control
CFW500 | 10-7
10
P0401 – Motor Rated Current
Adjustable
Range:
0.0 to 200.0 A
Factory
Setting:
1.0 x I
nom
P0402 – Motor Rated Speed
Adjustable
Range:
0 to 30000 rpm
Factory
Setting:
1710 rpm
(1425 rpm)
P0403 – Motor Rated Frequency
Adjustable
Range:
0 to 500 Hz
Factory
Setting:
60 Hz
(50 Hz)
Properties:
cfg
Access Groups
via HMI:
MOTOR, STARTUP
P0404 – Motor Rated Power
Adjustable
Range:
0 = 0.16 HP (0.12 kW)
1 = 0.25 HP (0.19 kW)
2 = 0.33 HP (0.25 kW)
3 = 0.50 HP (0.37 kW)
4 = 0.75 HP (0.55 kW)
5 = 1.00 HP (0.75 kW)
6 = 1.50 HP (1.10 kW)
7 = 2.00 HP (1.50 kW)
8 = 3.00 HP (2.20 kW)
9 = 4.00 HP (3.00 kW)
10 = 5.00 HP (3.70 kW)
11 = 5.50 HP (4.00 kW)
12 = 6.00 HP (4.50 kW)
13 = 7.50 HP (5.50 kW)
14 = 10.00 HP (7.50 kW)
15 = 12.50 HP (9.00 kW)
16 = 15.00 HP (11.00 kW)
17 = 20.00 HP (15.00 kW)
18 = 25.00 HP (18.50 kW)
19 = 30.00 HP (22.00 kW)
Factory
Setting:
According to
inverter model
P0407 – Motor Rated Power Factor
Adjustable
Range:
0.50 to 0.99
Factory
Setting:
0.80
Properties:
cfg, V VW
Access Groups
via HMI:
MOTOR, STARTUP
Description:
The setting of parameters P0401, P0402, P0403, P0404 and P0407 must be according to the data on the
nameplate of the motor used, taking into account the motor voltage.
Содержание CFW500 V1.8X
Страница 2: ......
Страница 4: ......
Страница 8: ...Contents...
Страница 34: ...General Information 2 4 CFW500...
Страница 38: ...About the CFW500 3 4 CFW500 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW500 4...
Страница 52: ...Programming Basic Instructions 5 10 CFW500 5...
Страница 56: ...Identification of the Inverter Model and Accessories 6 4 CFW500 6...
Страница 76: ...Available Motor Control Types 8 4 CFW500 8...
Страница 84: ...V f Scalar Control 9 8 CFW500 9...
Страница 170: ...Communication 17 8 CFW500 17...