Digital and Analog Inputs and Outputs
12-10 | CFW500
12
P0022 – Value of Frequency Input FI in Hz
Adjustable
Range:
0 to 20000 Hz
Factory
Setting:
Properties:
ro
Access Groups
via HMI:
READ, I/O
Description:
Value in hertz of the frequency input FI.
NOTE!
The operation of parameters P0021 and P0022, as well as of the frequency input, depends on the
activation of P0246.
P0246 – Frequency Input FI
Adjustable
Range:
0 = Inactive
1 = Active
Factory
Setting:
0
Properties:
Access Groups
via HMI:
I/O
Description:
When in "1" this parameter activates the frequency input, making the digital input DI2 function in P0264 be
ignored, as well as the value of Bit "1" of P0012 is maintained in "0". On the other hand, when in "0" the
frequency input is inactive keeping parameters P0021 and P0022 in zero.
P0247 – Input Gain in Frequency FI
Adjustable
Range:
0.000 to 9.999
Factory
Setting:
1.000
P0248 – Minimum Frequency Input FI
Adjustable
Range:
10 to 20000 Hz
Factory
Setting:
10 Hz
P0249 – Input Offset in Frequency FI
Adjustable
Range:
-100.0 to 100.0 %
Factory
Setting:
0.0 %
P0250 – Maximum Frequency Input FI
Adjustable
Range:
10 to 20000 Hz
Factory
Setting:
10000 Hz
Properties:
Access Groups
via HMI:
I/O
Содержание CFW500 V1.8X
Страница 2: ......
Страница 4: ......
Страница 8: ...Contents...
Страница 34: ...General Information 2 4 CFW500...
Страница 38: ...About the CFW500 3 4 CFW500 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW500 4...
Страница 52: ...Programming Basic Instructions 5 10 CFW500 5...
Страница 56: ...Identification of the Inverter Model and Accessories 6 4 CFW500 6...
Страница 76: ...Available Motor Control Types 8 4 CFW500 8...
Страница 84: ...V f Scalar Control 9 8 CFW500 9...
Страница 170: ...Communication 17 8 CFW500 17...