Functions Common to All the Control Modes
11-10 | CFW500
11
DC link voltage
F0021 level
Output pulses
t
dis
> t
dead
Enabled
Disabled
Return line
Output voltage
0 V
0 Hz
Output frequency
(P0002)
P0331
Figure 11.7:
Actuation of the Ride-Through function
The Ride-Through function allows recovering the inverter without locking by undervoltage F0021 for momentary
power supply drops. The time interval accepted during a fault is at most two seconds.
11.5 DC BRAKING
The DC Braking allows stopping the motor by applying direct current to it. The current applied at the DC Braking
is proportional to the braking torque and may be set in P0302. It is set in percentage (%) of the inverter rated
current considering the motor of power compatible with the inverter.
P0299 – DC Braking Time at Start
Adjustable
Range:
0.0 to 15.0 s
Factory
Setting:
0.0 s
Properties:
Access Groups
via HMI:
Description:
DC Braking duration at the start.
Direct current
injection at start
DC braking
Output frequency
Time
Run
Time
Stop
P0299
P0302
Figure 11.8:
DC Braking actuation at start
Содержание CFW500 V1.8X
Страница 2: ......
Страница 4: ......
Страница 8: ...Contents...
Страница 34: ...General Information 2 4 CFW500...
Страница 38: ...About the CFW500 3 4 CFW500 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW500 4...
Страница 52: ...Programming Basic Instructions 5 10 CFW500 5...
Страница 56: ...Identification of the Inverter Model and Accessories 6 4 CFW500 6...
Страница 76: ...Available Motor Control Types 8 4 CFW500 8...
Страница 84: ...V f Scalar Control 9 8 CFW500 9...
Страница 170: ...Communication 17 8 CFW500 17...