INSTALLATION AND CONNECTION
1
2
3
4
5
6
7
8
9
10 11 12
DI1
DI2
DI3
DI4
GND
GND
+10V
DO1-RL-NF
DO1-RL-C
DO1-RL-NA
Counter clockwise
≥
5k
Ω
Clockwise
(+)
(-)
Al1
Al1
(0 to 20) mA
(4 to 20) mA (0 to 10) V
(a)
NPN Configuration
1
2
3
4
5
6
7
8
9
10 11 12
DI1
DI2
DI3
DI4
GND
GND
+10V
DO1-RL-NF
DO1-RL-C
DO1-RL-NA
Counter clockwise
≥
5k
Ω
Clockwise
(+)
(-)
Al1
Al1
(0 to 20) mA
(4 to 20) mA (0 to 10) V
(External supply)
24V
(b)
PNP Configuration
Connector
Description
(*)
1
DI1
Digital Input 1
2
DI2
Digital Input 2
3
DI3
Digital Input 3
4
DI4
Digital Input 4
5
GND
Reference 0 V
6
Al1
Analog Input 1
(Current)
7
GND
Reference 0 V
8
Al1
Analog Input 1
(Voltage)
9
+10V
Ref10 Vdc
for potentiometer
10
DO1-RL-NC
Digital Output 1
(NC contact of relay 1)
11
DO1-RL-C
Digital Output 1
(Common point of relay 1)
12
DO1-RL-NO
Digital Output 1
(NO contact of relay 1)
(*)
For further information, refer to the detailed specification in
7.2 ELECTRONICS/GENERAL DATA on page 32
Figure 3.3:
(a) and (b) Signals of C320 control card connector
✓
NOTE!
The CFW320 inverters are supplied with the digital inputs configured as active low (NPN). In order
to change the configuration, check the use of parameter P271 in the programming manual of the
CFW320.
Analog input Al1 is set for input 0 to 10 V, in order to change, check parameter P233 of the
programming manual.
For the correct connection of the control, use:
1. Gauge of the cables: 0
.
5 mm
2
(20 AWG) a 1
.
5 mm
2
(14 AWG).
2. Maximum torque: 0
.
3 N.m (2
.
65 lbf.in).
3. Wiring of the connector of the control board with shielded cable and separated from the other wiring
(power, command in 110 V / 220 Vac, etc.), according to
Item 3.2.6 Cable Separation Distance on page 22
If those cables must cross other cables, it must be done in perpendiculary among them, keeping the
minimum separation distance of 5 cm at the crossing point.
Connect the shield according to the
.
CFW320 | 21
Содержание CFW320
Страница 1: ...Motors Automation Energy Transmission Distribution Coatings Frequency Inverter CFW320 User s Manual...
Страница 2: ......
Страница 41: ...APPENDIX A 1 1 Nameplate af xed to the side of the inverter Figure A2 Location of the nameplate CFW320 35...
Страница 45: ...APPENDIX A a Surface mounting b DIN rail mounting 1 2 3 c Removal of CFW320 on DIN Rail CFW320 39...
Страница 50: ...APPENDIX A Figure A11 Inverter dimensions in mm in frame size C 44 CFW320...