15-21
15
Faults and Alarms
15.4.2 PT100 or KTY84 Temperature Sensor Type
The parameters described in this section will be shown on the HMI when the IOE-02 or IOE 03 optional module
is connected into the slot 1 (XC41 connector). Refer to the
P0375 - Sensor 1 Fault/Alarm Temperature Setting
P0378 - Sensor 2 Fault/Alarm Temperature Setting
P0381 - Sensor 3 Fault/Alarm Temperature Setting
P0384 - Sensor 4 Fault/Alarm Temperature Setting
P0387 - Sensor 5 Fault/Alarm Temperature Setting
Adjustable
Range:
-20 to 200 ºC
Factory
Setting:
130 ºC
Properties:
-
Access groups
via HMI:
01 PARAMETER GROUPS
45 Protections
Description:
These parameters allow adjusting the temperature for each sensor, at which temperature fault/alarm will occur.
P0388 - Sensor 1 Temperature
P0389 - Sensor 2 Temperature
P0390 - Sensor 3 Temperature
P0391 - Sensor 4 Temperature
P0392 - Sensor 5 Temperature
Description:
These parameters indicate, in Celsius degrees, the PT100 or KTY84 sensor temperatures.
P0393 - Highest Sensor Temperature
Adjustable
Range:
-20 to 200 ºC
Factory
Setting:
-
Properties:
RO
Access groups
via HMI:
01 PARAMETER GROUPS
45 Protections
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...