13-13
13
Digital and Analog Inputs and Outputs
The indication is done by means of the numbers 1 and 0, representing respectively the "Active" and "Inactive" states of the
inputs. The state of each input is considered as one digit in the sequence where DI1 represents the least significant digit.
Example: In case the sequence
10100010
is presented on the keypad (HMI), it will correspond to the following
status of the DIs:
Table 13.8 -
Digital inputs status
DI8
DI7
DI6
DI5
DI4
DI3
DI2
DI1
Active
(+24 V)
Inactive
(0 V)
Active
(+24 V)
Inactive
(0 V)
Inactive
(0 V)
Inactive
(0 V)
Active
(+24 V)
Inactive
(0 V)
P0263 – DI1 Function
P0264 – DI2 Function
P0265 – DI3 Function
P0266 – DI4 Function
P0267 – DI5 Function
P0268 – DI6 Function
P0269 – DI7 Function
P0270 - DI8 Function
Adjustable
Range:
0 to 31
Factory
Setting:
P0263 = 1
P0264 = 8
P0265 = 0
P0266 = 0
P0267 = 10
P0268 = 14
P0269 = 0
P0270 = 0
Properties:
Access groups
via HMI:
07 I/O CONFIGURATION
or
01 PARAMETER GROUPS
40 Digital Input
40 Digital Input
Description:
Those parameters make it possible to configure the functions of the digital inputs, according to the adjustable range
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...