P0406 – Motor Ventilation
Adjustable
Range:
0 = Self-Ventilated
1 = Separate Ventilation
2 = Optimal Flux
3 = Extended Protection
Factory
Setting:
0
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
43 Motor Data
Description:
During the Oriented Start-up Routine, the value adjusted in P0406 changes the parameters related to the motor
overload automatically, in the following manner:
Table 11.2 -
Motor overload protection modification in function of P0406
P0406
P0156 (Overl.Curr.100 %)
P0157 (Overl.Curr.50 %)
P0158 (Overl.Curr.5 %)
0
1.05 x P0401
0.9 x P0401
0.65 x P0401
1
1.05 x P0401
1.05 x P0401
1.05 x P0401
2
1.05 x P0401
1.0 x P0401
1.0 x P0401
3
0.98 x P0401
0.9 x P0401
0.55 x P0401
ATTENTION!
Refer to the
Section 11.4 OPTIMAL FLUX FOR SENSORLESS VECTOR CONTROL on page 11-6
for more details on the use of option P0406 = 2 (Optimal Flux).
P0407 – Motor Rated Power Factor
Refer to the
Section 10.2 MOTOR DATA [43] on page 10-3
, for more details.
P0408 – Run Self-Tuning
P0409 – Motor Stator Resistance (Rs)
P0410 – Motor Magnetizing Current (I
m
)
P0411 – Motor Flux Leakage Inductance (
σ
ls)
P0412 – Lr/Rr Constant (Rotor Time Constant – T
r
)
P0413 – T
m
Constant (Mechanical Time Constant)
Self-Tuning function parameters. Refer to the
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...