11-11
11
Vector Control
P0398 – Motor Service Factor
Adjustable
Range:
1.00 to 1.50
Factory
Setting:
1.00
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
43 Motor Data
Description:
It is the continuous overload capability, i.e., a reserve of power that gives the motor the capability to withstand
working in adverse conditions.
Set it according to the value informed on the motor nameplate.
It affects the motor overload protection.
P0399 – Motor Rated Efficiency
Refer to the
Section 10.2 MOTOR DATA [43] on page 10-3
P0400 – Motor Rated Voltage
Adjustable
Range:
0 to 690 V
Factory
Setting:
220 V (P0296 = 0)
440 V (P0296 = 1, 2, 3 or 4)
575 V (P0296 = 5 or 6)
690 V (P0296 = 7 or 8)
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
43 Motor Data
Description:
Set it according to the motor nameplate data and to the motor cable wiring in the connection box.
This value cannot be higher than the rated voltage adjusted in P0296 (Line Rated Voltage).
NOTE!
In order to validate a new P0400 setting out of the Oriented Start-up Routine it is necessary to cycle
the power of the inverter.
P0401 – Motor Rated Current
Adjustable
Range:
0 to 1.3xI
nom-ND
Factory
Setting:
1.0xI
nom-ND
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
43 Motor Data
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...