Parameter
Description
Range of values
Decimal
places
Net Id
Size
Qty mapped
words
0 = Voltage Ramp
1 = Voltage Ramp + Current Limit
2 = Current Limit
3 = Current Ramp
4 = Pump Control
5 = Torque Control
6 = D.O.L. SCR
C1.2
Initial Start Voltage
25 to 90 %
0
101
8bit
1
C1.3
Maximum Start Time
1 to 999 s
0
102
16bit
1
C1.4
Start End Detection
106
enum
1
0 = Time
1 = Automatic
C1.5
Initial Current Ramp
150 to 500 %
0
111
16bit
1
C1.6
Current Ramp Time
1 to 99 %
0
112
8bit
1
C1.7
Current Limit
150 to 500 %
0
110
16bit
1
C1.8
Start Torque Chara.
120
enum
1
1 = Constant
2 = Linear
3 = Square
C1.9
Initial Start Torque
10 to 300 %
0
121
16bit
1
C1.10
End Start Torque
10 to 300 %
0
122
16bit
1
C1.11
Minimun Start Torque
10 to 300 %
0
123
16bit
1
C1.12
Min.Start Torq. Time
1 to 99 %
0
124
8bit
1
C1.13
Stop Time
0 to 999 s
0
104
16bit
1
C1.14
Step Down Volt. Stop
60 to 100 %
0
103
8bit
1
C1.15
End Voltage Stop
30 to 55 %
0
105
8bit
1
C1.16
Stop Torque Characte.
125
enum
1
1 = Constant
2 = Linear
3 = Square
C1.17
End Stop Torque
10 to 100 %
0
126
8bit
1
C1.18
Minimum Stop Torque
10 to 100 %
0
127
8bit
1
C1.19
Min. Stop Torque Time
1 to 99 %
0
128
8bit
1
C2 Configurations\Nominal Motor Data
C2.1
Voltage
1 to 999 V
0
400
16bit
1
C2.2
Current
0.1 to 2424.0 A
1
401
16bit
1
C2.3
Speed
1 to 3600 rpm
0
402
16bit
1
C2.4
Power
0.1 to 1950.0 kW
1
404
16bit
1
C2.5
P.F. Power Factor
0.01 to 1.0
2
405
8bit
1
C2.6
S.F. Service Factor
0.01 to 1.5
2
406
8bit
1
C3 Configurations\LOC/REM Selection
C3.1
Mode
220
enum
1
0 = Always LOC
1 = Always REM
2 = HMI LR Key LOC
3 = HMI LR Key REM
4 = DIx
5 = USB LOC
6 = USB REM
7 = SoftPLC LOC
SSW900
|
42